Vector V/f control (r0108.2 = 0)
5.4 Vdc control
Drive Functions
176 Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
Reduce the regenerative torque to maintain the DC link voltage within permissible
limits.
Undervoltage in the DC link
Typical cause
Failure of the supply voltage or supply for the DC link.
Remedy
Specify a regenerative torque for the rotating drive to compensate the existing losses,
thereby stabilizing the voltage in the DC link (kinetic buffering).
Properties
Vdc control
This comprises Vdc_max control and Vdc_min control (kinetic buffering), which are
independent of each other.
Joint PI controllers. The dynamic factor is used to set Vdc_min and Vdc_max control
to a smoother or harder setting independently of each other.
Vdc_min control (kinetic buffering)
With this function, the kinetic energy of the motor is used for buffering the DC link
voltage in the event of a momentary power failure, thereby delaying the drive.
Vdc_max control
This function can be used to control momentary regenerative load without shutdown
with “overvoltage in the DC link“.
Vdc_max control is only recommended with a supply without active closed-loop control
for the DC link and without feedback.
Description of Vdc_min control