Vector control
4.14 Instructions for commissioning induction motors (ASM)
Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
147
Parameter Description Remark
p0341 Motor moment of inertia -
p0342 Ratio between the total and motor
moment of inertia
-
p0344 Motor weight -
p0352 Cable resistance (component of the
stator resistance)
-
p0353 Motor series inductance -
Table 4-4 Equivalent circuit diagram for motor data
Parameter Description Remark
p0350 Motor stator resistance, cold -
p0354 Motor rotor resistance, cold -
p0356 Motor stator inductance -
p0358 Motor rotor leakage inductance -
p0360 Motor magnetizing inductance -
Features
● Field weakening up to approx. 1.2 * rated speed (this depends on the drive converter
supply voltage and the motor data, also refer to limitations/ constraints)
● Flying restart (for operation without encoder, only possible with additional VSM)
● Vector closed-loop speed and torque control
● Vector V/f control for diagnostics
● Motor identification
● Speed controller optimization (rotating measurement)
● Thermal protection via temperature sensor (PTC/KTY)
● All encoders that can be connected to an SMC10, SMC20 or SMC30 are supported.
● Operation with or without encoder is possible.
Supplementary conditions
Depending on the terminal voltage and load cycle, the maximum torque can be taken from
the motor data sheets / project design instructions.
Commissioning
We recommend the following points when commissioning:
● Commissioning Wizard in STARTER
The motor identification routine and the "rotating measurement" (p1900) can be activated
from the commissioning Wizard in STARTER.