Vector control
4.14 Instructions for commissioning induction motors (ASM)
Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
147
Parameter Description Remark
p0341 Motor moment of inertia -
p0342 Ratio between the total and motor
moment of inertia
-
p0344 Motor weight -
p0352 Cable resistance (component of the
stator resistance)
-
p0353 Motor series inductance -
Table 4-4 Equivalent circuit diagram for motor data
Parameter Description Remark
p0350 Motor stator resistance, cold -
p0354 Motor rotor resistance, cold -
p0356 Motor stator inductance -
p0358 Motor rotor leakage inductance -
p0360 Motor magnetizing inductance -
Features
Field weakening up to approx. 1.2 * rated speed (this depends on the drive converter
supply voltage and the motor data, also refer to limitations/ constraints)
Flying restart (for operation without encoder, only possible with additional VSM)
Vector closed-loop speed and torque control
Vector V/f control for diagnostics
Motor identification
Speed controller optimization (rotating measurement)
Thermal protection via temperature sensor (PTC/KTY)
All encoders that can be connected to an SMC10, SMC20 or SMC30 are supported.
Operation with or without encoder is possible.
Supplementary conditions
Depending on the terminal voltage and load cycle, the maximum torque can be taken from
the motor data sheets / project design instructions.
Commissioning
We recommend the following points when commissioning:
Commissioning Wizard in STARTER
The motor identification routine and the "rotating measurement" (p1900) can be activated
from the commissioning Wizard in STARTER.