Technical data
UPS MKD 1500 RT
Device and its Operation
MKD series
61
Contact your specialist dealer before you change the settings in this
menu. Incorrect settings may result in malfunctions or even UPS destruc-
tion.
The table below contains a description of the individual parameters.
Parameter
Possible settings
Default value
User password
<enable><disable>
If <enable> is selected, you have to enter the
password.
disable
Audio alarm
<enable><disable>
If <disable> is selected, the UPS is silent and
there are no alarm signals.
enable
Output voltage
<208V><220V> <230V> <240V>
230V
Output frequency
<50HZ><60HZ>
< Auto-sensing>
<50HZ>
Power strategy
<normal>
<high efficiency><converter>
Normal
DC start
<enable><disable>
Cold start
enable
Site wiring fault alarm
<enable><disable>
<enable> means that the UPS instantly issues
one warning signal if the phase and neutral
conductor have been swapped by mistake at
the mains input.
<disable> means that the UPS does not issue
a warning signal.
disable
Ambient temperature
warning
<enable><disable>
enable
Automatic battery tests
period
<0>…….<31days>
The automatic battery test is off if this value is
"0".
7days
Auto restart
<enable><disable>
<enable> means that the UPS performs an
automatic restart in normal mode if it was
powered down due to a low battery charge
status.
enable