Specifications

7
Rear view of ME 1000/1500
Rear view of ME 400-800VA
Models with USB
Rear view of ME 400-800VA
Models with RS232
Model ME 400 ME 500 ME 600 ME 650 ME 800 ME 1000 ME 1500
Input Voltage (VAC) 170-280VAC
Frequency (Hz) 50/60Hz
Synchronous zone 45-65Hz
Output (AC-Mode) AVR Regulation Boost +13%
Buck -13%
Output (INV.mode) Voltage 230VAC
+/-15% +/-10% +/-15%
Frequency 50/60Hz±1%
Waveform Modied sinewave
Capacity (VA/W) 400/225 500/250 600/300 650/325 800/425 1000/600 1500/900
Transfer time (ms) Typical 2-6ms Typical 4ms
Autonomy at full load in min. 6 6 4 4 3 5 4
Battery Voltage 12VDC 12VDC 12VDC 12VDC 12VDC 24VDC 24VDC
Type Maintainance free lead acid
Capacity 5Ah 7Ah 7Ah 7Ah 9.5Ah 7Ah 9.5Ah
Quantity 1 1 1 1 1 2 2
Recharging time 8 hours to 90% 6-8 hours to 90%
DC start Yes
Self diagnostics Upon power-on or software control
Indicator LED 2 LEDs (AC mode, battery mode, fault) 4 LEDs: line, backup, fault,
overload
Protection Overload AC mode Buzzer warning and fuse will open Continuous buzzer warning
INVmode Buzzer warning and UPS-shutdown >100% continuous warning
>110% UPS shut off after 10s
Short circuit AC mode: input fuse and elctronic circuit, Inv. Mode: electronic circuit
Noise suppression EN50091-2
Spike suppression - EN61000-4-5
Battery over-drain Battery low warning and UPS shut off
Modem / network RJ45
Alarm Audible Line failure, battery low Line failure, battery low, over-
load/fault
Physical Dimensions (HxWxD) 71x95x357mm 234x147x375mm
Net weight 5.4kgs 5.8kgs 5.8kgs 5.8kgs 6.4kgs 10.6kgs 14.2kgs
Outlet (IEC) 3 3 3 3 3 6 6
Environmental Operation temp. 0-40°C
Operation humidity 0-90% (non condensing) 0-95% (non condensing)
Communication Interface type RS232 SUB D 9 / optionally USB
Safety
conformance
Safety standard EN50091-1
EMC / surge standard EN50091-2, EN61000-3-2, EN61000-3-3
Mark CE
AC line-interactive UPS 400-3200VA
Specications