Specifications

81
GR 2000
Right hand image:
Block diagram
General
Efciency ≥ 91%
Losses, max. 200W
Safety EN 60 950, class I
EMI, radiated EN 55022, class B
Compliant with EN 300386-2
Cooling Fan cooled
Power density 500W/l (8.2W / in
3
)
User interface
Output current display LED bar
Status indication LEDs «ok», «Alarm»
Output voltage Test jack
Output current Test jack
Power system controller
PSC 1000 Voltage programming
Rectier fail alarm
PSC 1 / 3 (See brochure/data
sheet of power system controller)
Voltage programming
Current limit programming
Power limit programming
Rectier fail alarm
Rectier start up
Rectier on/off
Separate charge
Mechanics
Width, overall 65mm (2.56in)
Height, overall 212mm (8.35in)
Depth, overall 346mm (13.62in)
Weight 4.4kg (9.7lb)
Environment
Operating temperature -25 … +70°C (-13 … +158°F)
Power derating +60 … +70°C (+140 … +158°F)
Relative humidity 95% max., non condensing
Optional accessories
Single backplane D0100298
Blank panel D0018281
Input
Voltage range 88 … 276V
rms
Volt. range, red. power 88 … 184V
rms
Inrush current < 15A
peak
Current maximum 12A
rms
Line current According IEC 1000-3-2
Harmonic distort. THD < 5%
EMI, conducted EN 55022, class B
Mains connector Rear side
Input protection Internal fuse 2 x 15A
Input switch None
Output characteristic:
Modular DC power supply systems 48-60V
Specications
Specifications
Output
Voltage, nominal 53.5 / 62V
dc
Voltage adjust range 42 … 72V
dc
Voltage regulation ± 250mV
dc
Overvoltage protection 58.5 / 73V ± 1 %
Ripple + Spikes ≤ 200mV
pp
Psophometric noise ≤ 1.0mV
rms
(weighted)
EMI, conducted EN 55022, class A
Current limit, nominal 37A
dc
Limit adjustment range 0 … 37A
dc
Load sharing < ± 3A
dc
Power limit 2000W, xed
Output connector Rear side
Output protection Internal fuse 50A