Specifications

63
Batteries
Classication of the RTV modules
The battery modules (RTVC001 to RTVC004) are
designed exclusively for lead batteries with a nominal
connection voltage of 12V. The description section
CXXX species the corresponding capacity class.
This guarantees that the module type (RTVCXXX) is
suited to the intended battery capacity. The following
RTV modules are available:
Class: Capacity range: (battery
capacity)
Resistance range: (internal
resistance measurement)
IB/[A]* IP/[A]**
C001 7 – 12 Ah 1.1 – 110 mΩ 0 – 0.1 0.2
C002 >12 – 28 Ah 1.0 – 100 mΩ 0 – 0.3 0.6
C003 >28 – 65 Ah 0.6 – 60 mΩ 0 – 0.8 1.6
C004 >65 – 200 Ah 0.3 – 30 mΩ 0 - 3 4.6
Single module detail: board with temperature sensor Modules integrated into battery line
Module C004
Module C001
Single module Modules integrated into battery line Battery line on rail prepared for
integration into a Quasar
Module C003 on
BTL12-45 battery
Module C004 on
BTL6-100 battery
Single batteries