Specifications

43
AC large modular UPS 4-24kVA
Number of modules-
capacity
1
Module
2
Modules
3
Modules
4
Modules
5
Modules
6
Modules
4kVA N N+1 (4kVA) N+2 (8kVA) N+3 (12kVA) N+4 (16kVA) N+5 (20kVA)
8kVA N N+1 (4kVA) N+2 (8kVA) N+3 (12kVA) N+4 (16kVA)
12kVA N N+1 (4kVA) N+2 (8kVA) N+3 (12kVA)
16kVA N N+1 (4kVA) N+2 (8kVA)
20kVA N N+1 (4kVA)
24kVA N
Model MHD Modular
Capcity 4~24kVA
Input Singel / three phase Single phase Three phase
Wiring 1Ф2W + G 3Ф4W + G
Voltage 70% load 160~300VAC 277~520VAC
50-70% load 140~300VAC 242~520VAC
50% load 118~300VAC 204~520VAC
Input frequency 50/60 (1±8%) Hz
Power factor 0,98
Bypass 80~264VAC 140~457VAC
Phase Single phase
Output
Wiring 1Ф2W + G
Voltage 230 (±2%) VAC
Power factor 0,7
Output frequency Same as input frequency
50/60 (1±0,5%) Hz (backup mode)
Overload 110-130%, after 30 seconds transfer to bypass
>130%, after 2 seconds transfer to bypass
Capacity / module 4kVA
Output capacity 4kVA x number of modules
External batteries 120VDC (10 batteries in each cabinet)
Connect to generator Yes
Communication / interface RS232, RS485, intelligent slot
Weight Module 15kg
Cabinet 75kg
Dimensions of modules HxWxD in mm 88x430x530
Dimensions of cabinet HxWxD in mm 965x442x700
Battery capacity / autonomy time
Capacity VA Capacity
watt
Number of
modules
Autnomy
minutes
Battery conguration
4000 2800 1 30 120V-28Ah
4000 2800 1 40 120V-45Ah
4000 2800 1 60 2x120V-28Ah
4000 2800 1 90 120V-65Ah
8000 5600 2 10 120V-28Ah
8000 5600 2 25 120V-45Ah
8000 5600 2 30 2x120V-28Ah
8000 5600 2 45 3x120V-28Ah
Capacity VA Capacity
watt
Number of
modules
Autnomy
minutes
Battery conguration
12000 8400 3 15 2x120V-28Ah
12000 8400 3 20 120V-65Ah
12000 8400 3 30 3x120V-28Ah
16000 11200 4 10 2x120V-28Ah
16000 11200 4 15 120V-65Ah
16000 11200 4 20 3x120V-28Ah
20000 14000 5 15 3x120V-28Ah
20000 14000 5 25 2x120V-65Ah
24000 16800 6 10 3x120V-28Ah
24000 16800 6 20 2x120V-65Ah
Specications
Specifications