Specifications

29
Power (in kVA) Autonomy time in min.
(more info on request)
UPS dimensions
(H x W x D in mm)
Batterie cabinet dimensions
(H x W x D in mm)
Weight in kg
10 8 1220 x 530 x 950 305
20 1220 x 530 x 950 390
35 1220 x 530 x 950 475
15 12 1220 x 530 x 950 395
20 1220 x 530 x 950 480
30 1220 x 530 x 950 565
20 7 1220 x 530 x 950 380
15 1220 x 530 x 950 525
20 1220 x 530 x 950 610
25 5 1220 x 530 x 950 385
10 1220 x 530 x 950 530
15 1220 x 530 x 950 615
30 7 1220 x 530 x 950 535
12 1220 x 530 x 950 620
25 1220 x 530 x 950 1220 x 770 x 950 240 + 542
Type Z100 Z150 Z200 Z250 Z300
Power
Power in kVA 10 15 20 25 30
Power in kW 8 12 16 20 24
Cos phi 0.8
Input
Voltage 3 x 330-480VAC
Frequency 40-60Hz ± 20%
Power factor correction 0.95
Output
Voltage 1 x 220/230/240VAC, ± 1%
Current in ampere 43.5 65.2 86.9 108.7 130.4
Output voltage regulation ± 1%
Output regulation ( dynamic load ) ± 5%
Overload capacity 125% for 10 minutes / 150% for 5 seconds
Frequency 50/60Hz (± 0.1% synchronised) / 50/60Hz (± 0.005% xed)
Synchronisation range ± 1 or ± 4Hz selectable
Waveform Sine wave
Crestfactor 3:1
Harmonic distortion (THD) 100% load <3% linear load
Fault reaction Auto bypass mode / switch-off in case of overload, overtemp., short circuit
Efciency 91-92% with full batteries and 100% load / 89…91% @ 50% load
Batteries
Backuptime (100% load/ 50% load) min 20/46 12/27 7/16 5/11 7/16
DC voltage 384VDC
Number of blocks 32
Capacity 7-200Ah
Battery type Lead-acid, maintenance-free
Expected lifetime 5 years (optional 10 years)
Recharging time 6-8 hours to 90% capacity
Bypass (EUE)
Voltage 220/230/240V
Overload capacity 150% for 150 seconds / 1000% for 100 msec
Manuell bypass (standard) Yes
Communication
Display LCD display with 30 different alphanumeric / 8 status-messages
Acoustic alert Yes
Standard interface RS232 / Relays on terminal blocks and DB9 (24VDC/100mA), Mains o.k., Inverter, Battery low, Bypass ON
SNMP Optional via software or external adapter
Certicates & Tests
TÜV / CE IEC 950/EN 50091-1-1, CE
EMC / RFI EN 50091-2 «A»
Mechanics / enviroment
Enclosure Tower / colour: RAL7035 / IP 20
UPS dimensions (H x W x D in mm) 1220 x 530 x 950
battery cab. dimensions (H x W x D in mm) 1220 x 770 x 950
Weight in kg (UPS without batteries) 220 225 230 235 240
Temperature 0-40°C (UPS without batteries)
Rel. humidity 10-90% not condensing
Audible noise level at 1 metre 45 dbA
AC large UPS 6-300kVA
Specications