Specifications

23
AC large UPS 6-300kVA
MH 6000 Display MH 6000 (rear view) MH 6000 (adapter slot)
Specications
Specifications
Type MH 6000
Power
VA Rating 6000
Wattage 4200
Cos phi 0.7
Input
Voltage 160-280VAC
Frequency 45-65Hz
Current in Ampere 25
PFC (power-factor-correction) yes
Output
Voltage 200/220/230/240VAC selectable, ± 2%
Current in Ampere 21
Overload 110% for 125 sec./140% for 10 sec. - 2 cycles before switching to bypass
Frequency 50/60Hz (± 0,2 Hz in backup mode)
Waveform Pure sine wave
Crest factor 3:1
Harmonic distortion <3% with linear load
Fault reaction Automatic switch to bypass or disconnection (in case of overload, overheat or short circuit)
Efciency up to 91% / in eco mode up to 98%
BatterIES
Autonomy time (100% load) >8 min.
DC-voltage 240VDC
Number of blocs 20
Capacity per unit 7Ah
Type Lead acid, maintenance free (VRLA)
Expected lifetime 5 years (optional 10 years)
Recharge time <4 hours up to 90%
Bypass (SBS)
Nominal voltage 1 x 230V (160-280V)
Overload 200% for 160 msec.
Manuel bypass (standard) Yes
Communication
Display Status on LCD + LCD: Line Mode, Backup Mode, ECO Mode, Bypass supply, Battery Low,
Battery Bad/Disconnected, Overload, Transferring with Interruption & UPS Fault
Readings on LCD: Input Voltage, Input Frequency, Output Voltage, Output Frequency, Load percentage,
Battery Voltage & Inner Temperature
Alarms Audible and visual: Line Failure, Battery Low, Transfer to Bypass, System Fault Condition
Interface Standard RS232 interface, Communication slots options: 2nd RS232 & EPO, USB & EPO, RS 485 & EPO,
Relay contact & EPO, SNMP/WEBcard, etc.
SNMP Optional via software or external/slot adaptor
Certicates and tests
Security IEC 950/EN 50091-1, CE
EMV / RFI EN 55022 « A »
Mechanics / Environment
Casing Tower / colour black / protection type IP 21 / 748 x 290 x 645mm (H x W x D) / app. 86kg
Temperature 0-40°C (UPS without battery)
Humidity 10-90% (non condensing)
Audible noise 55 dB(A) in 1 m distance (depends on load and temperature)