19
AC online double-conversion UPS 700-3000VA
Rear view MKD 2000Rear view MKD 700/1000 Rear view MKD 3000
Type MKD 700 MKD 1000 MKD 2000 MKD 3000
Power Power in VA
700 1000 2000 3000
Power in W 490 700 1400 2100
Autonomy time Nominal load 10 7 7 6
Input Nominal input voltage 230VAC
Input voltage range
118~300VAC (0-50% load), 140~300VAC (50-70% load), 160~300VAC (70-100% load)
Input frequency range
50 or 60Hz +/-8%
Max. input current
s. terminals > input fuse
Powerfactor (cos φ)
>0.95 >0.97
Output Output voltage
adjustable 220, 230, 240VAC
Deviation statically
+/-2%
Waveform
Sine wave
Output frequency 50 or 60Hz (synchronized line-mode / ± 0.5% battery mode)
Harmonic distortion / linear load < 3% @ full load < 4% @ full load
Crest factor acc. EN 50091-1 3:1 / (surge current / RMS-current)
Max. output current in A
3 4.3 8.7 13
Efciency at nom. Load
>85% AC-AC / >83% DC-AC
Overload Normal operation mode
Bypass transfer @ load > 110%
Normal / battery mode
105-150% for 30Sec. / 150% for 200mSec
Short circuit current
3 x Inenn for (120mSec)
Bypass Voltage range
Adjustment range min. 156-196V, max. 233-273V
Transfer time
2.5mSec inverter to bypass
Battery Nom. Voltage
36VDC 36VDC 96VDC 96VDC
Blocks
3
3 8 8
Nom. capacity/block
7Ah 7Ah 7Ah 7Ah
Type
Lead acid, maintenance free batteries
Life time
App. 5 years (subject to environment)
Recharge time
App. 5h up to 90%
Battery test
Manually via button or via software
Prot./standards Appliances
Electron. overload- and short circuit-prot., temperature monitoring, deep discharge protection…
Safety
CE / EN62040-1
EMC
EN 62040-2
Environment Temperature (operational)
0°C – 40°C
Temperature (storage)
0°C – 40°C
Humidity
20-95% not condensing
Altitude (operational)
<2000m o. NN
Mechanic Casing
Steel plate / front plastics
Protection class IP20
Dimensions (H x W x D in mm) 220x160x400 220x160x400 352x200x450 352x200x450
Weight 15kgs 15kgs 34kgs 35kgs
Terminals Input 1 x IEC (10A) 1 x IEC (16A)
Output 4 x IEC 6 x IEC 3 x IEC (10A)
1 x IEC (16A)
Input fuse 6.3A 6.3A 10A 16A
DC-terminals (for ext. battery extension) Only XL-models
Communication Socket Sub-D 9, slot RS 232-interface / Optionally available cards for slot: USB, relays, SNMP