III. ELECTRICAL HOOK-UP
WARNING
BEFORE DOING ANY WORK ON THE UNIT BE SURE THE
BREAKER IS “OFF” TO AVOID ANY DANGER OF SHOCK.
“Eemax ProAdvantage” heaters are manufactured to the following specifications:
The L1, L2, or N should be connected to the slots in the contactor marked L1 and L2.
(see Fig 2b). The ground lead must be connected to the stud marked GND.
GROUND MUST BE BROUGHT TO THE “GROUNDAT THE CIRCUIT BREAKER PANEL.
Use a dedicated circuit with appropriate wiring and circuit breaker configuration which is
dictated by the power requirements of the unit. (see Table 1 and Fig 3)
DANGER
FAILURE TO GROUND THE SYSTEM MAY RESULT IN DEATH OR SERIOUS INJURY.
MODEL TYPE Voltage kW output AMPERAGE
PA004120T 1f 120V 3.5 29
PA008208T 1f 208V 8.3 40
PA005240T 1f 240V 4.8 20
PA007240T 1f 240V 6.5 27
PA010240T 1f 240V 9.5 40
PA012240T 1f 240V 11.5 48
PA008277T 1f 277V 8.0 29
PA010277T 1f 277V 10.0 36
Table 1
7
Figure 3
Dedicated
Single Pole (120/277 Volts)
or
Double Pole (208/240 Volts)
Circuit
ON
OFF
or
Circuit Breaker Panel
ON
ON
OFF
OFF