Manual ED020-032 T3-T2T

EX09001-48 REV 8
6
ELECTRICAL HOOK-UP
WARNING
HAZARD OF ELECTRICAL SHOCK! BEFORE BEGINNING ANY WORK ON THE
INSTALLATION, MAKE SURE THE ELECTRICAL SUPPLY TO THE HEATER IS TURNED
“OFF”. FAILURE TO DO THIS COULD RESULT IN DEATH, SERIOUS BODILY INJURY,
OR PROPERTY DAMAGE.
WARNING
WATER HEATERS EQUIPPED FOR ONE VOLTAGE ONLY: CHECK THE RATING PLATE
ON THE FRONT OF THE UNIT. DO NOT USE THIS WATER HEATER WITH ANY VOLTAGE
OTHER THAN THE ONE SHOWN ON THE MODEL RATING PLATE. FAILURE TO DO SO
CAN RESULT IN DEATH, SERIOUS BODILY INJURY, OR PROPERTY DAMAGE. IF YOU
HAVE ANY QUESTIONS OR DOUBTS CONSULT YOUR ELECTRIC COMPANY.
This heater must have its own independent circuit using four wires; three live and one earth ground,
of the appropriate rating protected by the correctly rated three pole breaker
WARNING
FAILURE TO GROUND THE SYSTEM MAY RESULT IN DEATH OR SERIOUS INJURY
RATINGS OF “ED” Series Three Electric Tankless Water Heater
THIS UNIT MUST NOT BE CONNECTED IN STAR CONFIGURATION
Temperature Rise (F°) GPM
(gallons per minute)
Model number
prefix kW Rating
Amps per phase
2 gpm 3 gpm 4 gpm
T3 and T3 EE
Only
5 gpm
6 gpm
ED020 20 24 68 46 34 27 23
ED024 24 29 82 55 41 33 27
ED032 32 35.5 110 73 55 43 36