Specification Sheet
Information and product specications contained in this document are subject to change without notice. REV 2020-01
Specications
Tankless Electric Water Heater
SafeAdvantage (NEMA 4 Incl.)
For Safety Applications – Eye/Face Wash and Drench Showers
Typical Safety Shower - Piping Installation Schematic
Below represents a recommended installation of our SafeAvantage
heater for safety shower application. Please note the required use
of water hammer arrestors, Y-strainer, ball valves and drains.
EEMAX
MODEL
BALL VALVE
DRAIN
1-1/4" DIELECTRIC UNION
PRESSURE
REGULATING
VALVE
(60-90 PSI)
Y- STRAINER
40 MESH
HEADER
PIPE
(2-1/2" DIA
or larger)
HAMMER
ARRESTOR
(required)
EMERGENCY
SHOWER
VALVE
10 FT
MAX
1-1/4" DIA
1-1/4" DIA
Pipe Length (header to shower) Arrestor Size
15'
B
15' - 30'
C
30' - 50'
D
50' - 75'
E
75' - 90'
F
90' +
Contact Arrestor Mfgr
Water Hammer Arrestor Sizing Chart
System Criteria
Max Flow Rate: 30 GPM
Pipe Diameter: 1-1/4" or larger
Optimum Operating Pressure: 60-90 PSI