Installation Guide and Manual
6
Electrical Specifications
MODEL
VOLTS
3-PHASE DELTA
KW
AMPS
PER PHASE
RECOMMENDED
WIRE SIZE (CU) 90° C
AP032208
208
32
89
1 AWG
AP036208
208
36
100
1 AWG
AP041208
208
41
114
1 AWG
AP054208
208
54
150
2/0
AP064208
208
64
178
3/0
AP036480
480
36
44
8 AWG
AP039480
480
39
47
8 AWG
AP048480
480
48
58
6 AWG
AP054480
480
54
65
4 AWG
AP063480
480
63
76
3 AWG
AP072480
480
72
86
3 AWG
AP096480
480
96
116
1 AWG
AP108480
480
108
130
1/0
AP126480
480
126
152
2/0
AP144480
480
144
173
3/0
AP048600
600
48
47
8 AWG
AP051600
600
51
50
6 AWG
AP061600
600
61
59
6 AWG
AP071600
600
71
69
4 AWG
AP102600
600
102
99
1 AWG
AP130600
600
130
130
1 AWG
AP150600
600
150
145
1/0
A green terminal (or a wire connector marked “G”, “GR, “Ground”, or “GROUNDING”) is provided within
the control box. To reduce the risk of electric shock, connect this terminal or connector to the grounding
terminal of the electric service or supply panel with a continuous copper wire in accordance with your
local electrical code.