Cut Sheet

www.edwardssignaling.com
1-124
TM
VISUAL SIGNALS
1
Ordering Information
Description Cat. No.
Operating
Voltage
1
Current
Lens
Colors
Peak
Candela
Replacement
Lens Strobe Tube
Xenon Strobe
AC
96BA-N5 120V AC 0.10 A Amber 300,000 96-LA
91B-ST
3,000 hours
2
96BB-N5 120V AC 0.10 A Blue 300,000 96-LB
96BC-N5 120V AC 0.10 A Clear 300,000 96-LC
96BG-N5 120V AC 0.10 A Green 300,000 96-LG
96BM-N5 120V AC 0.10 A Magenta 300,000 96-LM
96BR-N5 120V AC 0.10 A Red 300,000 96-LR
96BA-R5 240V AC 0.02 A Amber 300,000 96-LA
91B-ST
3,000 hours
2
96BB-R5 240V AC 0.02 A Blue 300,000 96-LB
96BC-R5 240V AC 0.02 A Clear 300,000 96-LC
96BG-R5 240V AC 0.02 A Green 300,000 96-LG
96BM-R5 240V AC 0.02 A Magenta 300,000 96-LM
96BR-R5 240V AC 0.02 A Red 300,000 96-LR
Xenon Strobe
DC
98BA-E1 12V DC 0.5 A Amber 300,000 96-LA
91B-ST
3,000 hours
2
98BB-E1 12V DC 0.5 A Blue 300,000 96-LB
98BC-E1 12V DC 0.5 A Clear 300,000 96-LC
98BG-E1 12V DC 0.5 A Green 300,000 96-LG
98BM-E1 12V DC 0.5 A Magenta 300,000 96-LM
98BR-E1 12V DC 0.5 A Red 300,000 96-LR
98BA-G1 24V DC 0.3 A Amber 300,000 96-LA
91B-ST
3,000 hours
2
98BB-G1 24V DC 0.3 A Blue 300,000 96-LB
98BC-G1 24V DC 0.3 A Clear 300,000 96-LC
98BG-G1 24V DC 0.3 A Green 300,000 96-LG
98BM-G1 24V DC 0.3 A Magenta 300,000 96-LM
98BR-G1 24V DC 0.3 A Red 300,000 96-LR
1
AC voltage frequency is 50/60 Hz
2
Calculated at operating power to 75% efficiency.
Edwards 96B and 98B Series Xenon strobe
beacons are light duty visual signals suitable for
use in industrial, commercial and institutional
applications where short term intermittent visual
signaling is required. Both series feature a
corrosion resistant NEMA Type 4X enclosure and
can be panel or conduit mounted. Optically
designed fresnel lenses improve viewer
perception for indoor and outdoor applications.
The 96B and 98B Series are often used where a
smaller output is desired or where multiple,
smaller strobes are required. Trigger and timing
circuits are included as integral parts of the power
supply. Replacement costs are reduced, as it is
necessary to replace only the strobe tube.
Features and Specifications
Xenon strobe light source
Flash rate 65 fpm
Snap-on high impact plastic base
Optically designed fresnel lenses
Resistant to shock and vibration
Suitable for indoor and outdoor applications
For outdoor use, lens should face up
NEMA Type 4X enclosure
Option for panel or conduit mounting
Operating temperature range: -31°F to 150°F
(-35°C to 66°C)
Beacons
Flashing Xenon
96 and 98 Series
150°F
-31°F
OP TEMP
AC
DC
ENCLOSURE
4X
*AC versions only
*
XENON
4.28"
R A G B
CM

Summary of content (2 pages)