Cut Sheet
Page 4 of 6 D A T A S H E E T S85001-0341
Not to be used for installation purposes. Issue 6.1
Rated Strobe Output - candela (cd) 2447TH-R 2452THS-15/75-R 2452THS-110-R
UL 1638
N/A (horn only)
75 cd 110 cd
UL 1971
15 cd wall
15 cd ceiling
110 cd wall
60 cd ceiling
ULC S526 75 cd 120 cd
Standalone Synchronization
Characteristics (note 2)
Strobe flash at 1 per second within 200 milliseconds on common circuit Horn pulses at temporal rate
within 200 milliseconds on common circuit
Operating Volts
Strobe: 16-33 Vdc or Vfwr Continuous
Horn: 16-33 Vdc or Vfwr Continuous
Horn Output (note 1)
Anechoic: High Setting - 104 dBA (peak)/98 dBA (avg); Low Setting - 99 dBA (peak)/94 dBA (avg)
Reverberent: High Setting - 85 dBA (continuous)/82 dBA (temporal);
Low Setting - 82 dBA (continuous)/75 dBA (temporal)
Horn Current
High Output: 40 mA @ 24 Vdc; 55mA @ 24 Vrms FWR
Low Output: 20 mA @ 24 Vdc; 28 mA @ 24 Vrms FWR
Strobe Flash Synchronization
Synchronized at one flash per second. External control module necessary to meet UL 1971 synchronization
requirements of 10 milliseconds over a two-hour period.
Synchronization Sources EG1M-RM, EBPS6A, EBPS10A, E-NAC, E-FSC, E-FSA
Strobe Marking
Supplied with LKW-1 “FIRE” red letters, vertical both sides (Wall Mount) - see LKW and LKC series for ceiling
style and optional markings.
Flash Tube Enclosure Clear LEXAN with white marking sleeve
Housing Textured, color impregnated engineered plastics - exceeds 94V-0 UL flammability rating
Wire Connections Terminals - separate, polarized inputs for Horn & Strobe, #12 AWG (2.5mm²) maximum
INDOOR Operating Environment 32-120° F (0-49° C) ambient temperature. 93% relative humidity @ 40° C
OUTDOOR Operating Environment
(must use weatherproof box)
98% relative humidity @ 40° C
-31-150° F (-35-66° C) ambient temperature
Mounting - INDOOR
Flush: North-American 2-gang box, 3” high x 4” wide x 2¾” (69 mm) minimum
Surface: 2459-SMB-R Back box Bi-directional: 2400A-BDF Mounting Frame
Mounting - OUTDOOR Surface: 2459-WPB-R Weatherproof Box
Agency Listings
UL 1971, UL 1638, UL 464, ULC S526, ULC S525, MEA, CSFM, FM
(All models comply with ADA Code of Federal Regulation Chapter 28 Part 36 Final Rule)
Specifications
Light Output Patterns
Note 1 - Measured at 10 ft (3m) @ 24 Vdc. Subtract 3 dBA for models with strobes. Note 2 - Temporal audible pattern is defined as: ½ sec ON, ½ sec OFF, ½ sec ON, ½ sec
OFF, ½ sec ON, 1½ sec OFF, then repeat cycle. Integrity audible will not be affected by Genesis signal silence operation when on the same two wire circuit with Genesis horn
strobes.
Vertical
Horizontal
90°
90°
-90°
-90°
15 cd (-5A) Series Strobes
Horizontal Output
UL min
Average
Vertical Output
30 20
10 10 20 30
cd
-90
-75
-60
-45
-30
-15
0
15
30
45
60
75
90
d
e
g
r
e
e
s
30
20
10
10
20
30
cd
-90
-75
-60
-45
-30
-15
0
15
30
45
60
75
90
d
e
g
r
e
e
s
100100 10050 cd 50
d
e
g
r
e
e
s
-90
-75
-60
-45
-30
-15
0
15
30
45
60
75
90
100
100
50
50
cd
-90
-75
-60
-45
-30
-15
0
15
30
45
60
75
90
d
e
g
r
e
e
s
15/75 cd (-7A) Series Strobes
Horizontal Output
UL min
Average
Vertical Output
60
6040
40
cd
20
20
d
e
g
r
e
e
s
-90
-75
-60
-45
-30
-15
0
15
30
45
60
75
90
60
60
40
40
cd
20
20
-90
-75
-60
-45
-30
-15
0
15
30
45
60
75
90
d
e
g
r
e
e
s
30 cd (-3A) Series Strobes
Horizontal Output
UL min
Average
Vertical Output
200
200
100
100
cd
d
e
g
r
e
e
s
-90
-75
-60
-45
-30
-15
0
15
30
45
60
75
90
150
150
100
100
cd
50
50
-90
-75
-60
-45
-30
-15
0
15
30
45
60
75
90
d
e
g
r
e
e
s
110 cd (-8A) Series Strobes
Horizontal Output
UL min
Average
Vertical Output
75 cd (-4A) Series Strobes
Horizontal Output
UL min
Average
Vertical Output
140
100
cd
60
d
e
g
r
e
e
s
-90
-75
-60
-45
-30
-15
0
15
30
45
60
75
90
140
100
60
140
140
100
100
cd
60
60
-90
-75
-60
-45
-30
-15
0
15
30
45
60
75
90
d
e
g
r
e
e
s
Vertical
Horizontal
90°
90°
-90°
-90°