Owner manual

P/N 3100179 ISSUE 1 PAGE 8
SW1 SW2 SW3 SW4 SW5 SW6 SW7 SW8
BAUD RATE - 125 Kbps 0 0
BAUD RATE - 250 Kbps 0 1
BAUD RATE - 500 Kbps 1 0
BAUD RATE - 125 Kbps 1 1
MAC ID 0 000000
MAC ID 1 000001
MAC ID 2 000010
MAC ID 3 000011
MAC ID 4 000100
MAC ID 5 000101
MAC ID 6 000110
MAC ID 7 000111
MAC ID 8 001000
MAC ID 9 001001
MAC ID 10 (0x0A) 001010
MAC ID 11 (0x0B) 001011
MAC ID 12 (0x0C) 001100
MAC ID 13 (0x0D) 001101
MAC ID 14 (0x0E) 001110
MAC ID 15 (0x0F) 001111
MAC ID 16 (0x10) 010000
MAC ID 17 (0x11) 010001
MAC ID 18 (0x12) 010010
MAC ID 19 (0x13) 010011
MAC ID 20 (0x14) 010100
MAC ID 21 (0x15) 010101
MAC ID 22 (0x16) 010110
MAC ID 23 (0x17) 010111
MAC ID 24 (0x18) 011000
MAC ID 25 (0x19) 011001
MAC ID 26 (0x1A) 011010
MAC ID 27 (0x1B) 011011
MAC ID 28 (0x1C) 011100
MAC ID 29 (0x1D) 011101
MAC ID 30 (0x1E) 011110
Pin 1 (+) + 24V DC Red Wire
Pin 2 (-) - 24V DC Black Wire
2. A two (2) position screw terminal is provided to connect separate 24V DC light source operating power to the
Chameleon DeviceNet Status Indicator. The terminals for the 24V DC unit are labeled as "+" and "-". Make
connections as follows:
3. If it is desired to power the light sources from DeviceNet power, jumper (V+) and (V-) on the 5 position DeviceNet
terminal block to (+) and (-) respectively on the 2 position screw terminal.
Set DIPSWITCH S1 for the BAUD RATE and MAC ID required as follows:
Note the legend on the dipswitch for the sense of 0 and 1 (0 = OFF and 1 = ON)