Instruction Manual
P/N 3100125 ISSUE 3PAGE 5
For Units Configured with 3 Light Modules
BYTE BIT7 BIT6 BIT5 BIT4 BIT3 BIT2 BIT1 BIT0
0 DON'T DON'T DON'T DON'T DON'T LMP 3 LMP 2 LMP 1
CARE CARE CARE CARE CARE 1 = ON 1 = ON 1 = ON
0 = OFF 0 = OFF 0 = OFF
1 0 0 1 DON'T DON'T LMP 3 LMP 2 LMP 1
45 CARE CARE 1 = FLSH 1 = FLSH 1 = FLSH
FPM 0 = STDY 0 = STDY 0 = STDY
1 0 1 0 DON'T DON'T LMP 3 LMP 2 LMP 1
60 CARE CARE 1 = FLSH 1 = FLSH 1 = FLSH
FPM 0 = STDY 0 = STDY 0 = STDY
1 1 DON'T DON'T DON'T DON'T LMP 3 LMP 2 LMP 1
80 CARE CARE CARE CARE 1 = FLSH 1 = FLSH 1 = FLSH
FPM 0 = STDY 0 = STDY 0 = STDY
1 0 0 0 DON'T DON'T LMP 3 LMP 2 LMP 1
80 FPM 80 FPM 80 FPM CARE CARE 1 = FLSH 1 = FLSH 1 = FLSH
DEFLT DEFLT DEFLT 0 = STDY 0 = STDY 0 = STDY
2 DON'T DON'T DON'T DON'T Sounder Tone Tone Tone
CARE CARE CARE CARE 1 = ON MSB LSB
0 = OFF
For Units Configured with 2 Light Modules
BYTE BIT7 BIT6 BIT5 BIT4 BIT3 BIT2 BIT1 BIT0
0 DON'T DON'T DON'T DON'T DON'T DON'T LMP 2 LMP 1
CARE CARE CARE CARE CARE CARE 1 = ON 1 = ON
0 = OFF 0 = OFF
1 0 0 1 DON'T DON'T DON'T LMP 2 LMP 1
45 CARE CARE CARE 1 = FLSH 1 = FLSH
FPM 0 = STDY 0 = STDY
1 0 1 0 DON'T DON'T DON'T LMP 2 LMP 1
60 CARE CARE CARE 1 = FLSH 1 = FLSH
FPM 0 = STDY 0 = STDY
1 1 DON'T DON'T DON'T DON'T DON'T LMP 2 LMP 1
80 CARE CARE CARE CARE CARE 1 = FLSH 1 = FLSH
FPM 0 = STDY 0 = STDY
1 0 0 0 DON'T DON'T DON'T LMP 2 LMP 1
80 FPM 80 FPM 80 FPM CARE CARE CARE 1 = FLSH 1 = FLSH
DEFLT DEFLT DEFLT 0 = STDY 0 = STDY
2 DON'T DON'T DON'T DON'T Sounder Tone Tone Tone
CARE CARE CARE CARE 1 = ON MSB LSB
0 = OFF