Instruction Manual
P/N 3100125 ISSUE 3 PAGE 4
For Units Configured with 4 Light Modules
BYTE BIT7 BIT6 BIT5 BIT4 BIT3 BIT2 BIT1 BIT0
0 DON'T DON'T DON'T DON'T LMP 4 LMP 3 LMP 2 LMP 1
CARE CARE CARE CARE 1 = ON 1 = ON 1 = ON 1 = ON
0 = OFF 0 = OFF 0 = OFF 0 = OFF
1 0 0 1 DON'T LMP 4 LMP 3 LMP 2 LMP 1
45 CARE 1 = FLSH 1 = FLSH 1 = FLSH 1 = FLSH
FPM 0 = STDY 0 = STDY 0 = STDY 0 = STDY
1 0 1 0 DON'T LMP 4 LMP 3 LMP 2 LMP 1
60 CARE 1 = FLSH 1 = FLSH 1 = FLSH 1 = FLSH
FPM 0 = STDY 0 = STDY 0 = STDY 0 = STDY
1 1 DON'T DON'T DON'T LMP 4 LMP 3 LMP 2 LMP 1
80 CARE CARE CARE 1 = FLSH 1 = FLSH 1 = FLSH 1 = FLSH
FPM 0 = STDY 0 = STDY 0 = STDY 0 = STDY
1 0 0 0 DON'T LMP 4 LMP 3 LMP 2 LMP 1
80 FPM 80 FPM 80 FPM CARE 1 = FLSH 1 = FLSH 1 = FLSH 1 = FLSH
DEFLT DEFLT DEFLT 0 = STDY 0 = STDY 0 = STDY 0 = STDY
2 DON'T DON'T DON'T DON'T Sounder Tone Tone Tone
CARE CARE CARE CARE 1 = ON MSB LSB
0 = OFF
Output to the 102TBS-DN with the poll command from master node.
Data Byte 0 value indicates the lamps to be turned ON or OFF.
Data Byte 1 value indicates the ON lamps to be Steady ON or Flashing and the Flashing rate (45, 60 or 80 flashes
per minute) selected. Strobe units should always be set to Steady ON.
Data Byte 2 value indicates the sounder to be turned ON or OFF and the tone to be chosen.
For Units Configured with 5 Light Modules
BYTE BIT7 BIT6 BIT5 BIT4 BIT3 BIT2 BIT1 BIT0
0 DON'T DON'T DON'T LMP 5 LMP 4 LMP 3 LMP 2 LMP 1
CARE CARE CARE 1 = ON 1 = ON 1 = ON 1 = ON 1 = ON
0 = OFF 0 = OFF 0 = OFF 0 = OFF 0 = OFF
1 0 0 1 LMP 5 LMP 4 LMP 3 LMP 2 LMP 1
45 1 = FLSH 1 = FLSH 1 = FLSH 1 = FLSH 1 = FLSH
FPM 0 = STDY 0 = STDY 0 = STDY 0 = STDY 0 = STDY
1 0 1 0 LMP 5 LMP 4 LMP 3 LMP 2 LMP 1
60 1 = FLSH 1 = FLSH 1 = FLSH 1 = FLSH 1 = FLSH
FPM 0 = STDY 0 = STDY 0 = STDY 0 = STDY 0 = STDY
1 1 DON'T DON'T LMP 5 LMP 4 LMP 3 LMP 2 LMP 1
80 CARE CARE 1 = FLSH 1 = FLSH 1 = FLSH 1 = FLSH 1 = FLSH
FPM 0 = STDY 0 = STDY 0 = STDY 0 = STDY 0 = STDY
1 0 0 0 LMP 5 LMP 4 LMP 3 LMP 2 LMP 1
80 FPM 80 FPM 80 FPM 1 = FLSH 1 = FLSH 1 = FLSH 1 = FLSH 1 = FLSH
DEFLT DEFLT DEFLT 0 = STDY 0 = STDY 0 = STDY 0 = STDY 0 = STDY
2 DON'T DON'T DON'T DON'T Sounder Tone Tone Tone
CARE CARE CARE CARE 1 = ON MSB LSB
0 = OFF