Instruction Manual

P/N 3100125 ISSUE 3 PAGE 2
1.3 Object Interfaces:
OBJECT Effect on Behavior
Identity (1) Message router
Message Router (2) Explicit message connection instance
Devicenet (3) Message router
Assembly (4) I/O connection or message router
Connection (5) Message router
1.4 Identification of I/O Assembly Interfaces:
Instance Number Type Name
1 Input/Output Lamps ON/OFF, Lamp diagnostics, and sounder control
1.5 Format of I/O Assembly data Attribute:
Input to the DeviceNet bus as a response to the poll command from master node.
Data Byte 0 value indicates the lamp is OK or it is either burned out or missing.
Data Byte 1 value indicates the lamp was on or off when last poll command was received.
Data Byte 2 value indicates the current sounder module control value.
For Units Configured with 5 Light Modules
BYTE BIT7 BIT6 BIT5 BIT4 BIT3 BIT2 BIT1 BIT0
0 PWR FAIL DON'T DON'T LMP 5 LMP 4 LMP 3 LMP 2 LMP 1
1=PWR LOST CARE CARE 1 = REP 1 = REP 1 = REP 1 = REP 1 = REP
2=PWR OK 0 = OK 0 = OK 0 = OK 0 = OK 0 = OK
1 DON'T DON'T DON'T LMP 5 LMP 4 LMP 3 LMP 2 LMP 1
CARE CARE CARE 1 = ON 1 = ON 1 = ON 1 = ON 1 = ON
0 = OFF 0 = OFF 0 = OFF 0 = OFF 0 = OFF
2 DON'T DON'T DON'T DON'T Sounder Tone Tone Tone
CARE CARE CARE CARE 1 = ON MSB LSB
0 = OFF
For Units Configured with 4 Light Modules
BYTE BIT7 BIT6 BIT5 BIT4 BIT3 BIT2 BIT1 BIT0
0 PWR FAIL DON'T DON'T DON'T LMP 4 LMP 3 LMP 2 LMP 1
1=PWR LOST CARE CARE CARE 1 = REP 1 = REP 1 = REP 1 = REP
2=PWR OK 0 = OK 0 = OK 0 = OK 0 = OK
1 DON'T DON'T DON'T DON'T LMP 4 LMP 3 LMP 2 LMP 1
CARE CARE CARE CARE 1 = ON 1 = ON 1 = ON 1 = ON
0 = OFF 0 = OFF 0 = OFF 0 = OFF
2 DON'T DON'T DON'T DON'T Sounder Tone Tone Tone
CARE CARE CARE CARE 1 = ON MSB LSB
0 = OFF