Technical data

EDS - TECHNICAL INSTRUCTIONS
7
15 - FRONTAL LEDS OPERATION
15.1 - the frontal leds of the RX during the normal operation of
the detector, give out the following indications (see fig.9):
normal operation: the blue led flashes every 10 seconds
alarm: the red led is constantly ON
limit of compensation, interrupted beam, fault: the blue Led
flashes every second
16 - MAINTENANCE
16.1 - the instrument requires an easy and periodic maintenance.
It can be programmed or made automatic using remote signaling
of the detector.
During the normal operation and after a certain time from
installation, if maintenance is not performed, the detector, because
of the dirt and dust deposited on the front of the covers, gives out
a fault output signal, because of the decrease of the signal below
the limit of compensation.
Then it will be time to proceed to cleaning in order to reestablish
the initial optical conditions.
16.2 - The operations to be done are the following :
• remove power supply
• verify the inside terminal board tightening the terminals in the
case they are loose
• verify the optical alignment in case some changes of the structure
on which the detector is installed. In this case repeat the operations
of chap.8
• perform the cleaning of the front covers of TX and RX.
We suggest to use a wet cloth with water with some trace of soap.
Chemical products like alcohol, ammonia and similar must not be
used. The cleaning of the frontcover is fundamental for the good
operation of the device
• power up the devioce
17 - SENSITIVITY SELECTION
17.1- Afer the installation and after some working time, if you
want to modify the sensitivity of the detector, read what follow:
remove the cover of the receiver (it is not necessary to power
off the detector)
• modify the sensitivity acting on the SW2 selector
• close the cover
TECHNICAL DATA
Models: RK100B, RK200B
Type: Barrier Optical Beam Smoke Detector
Manufacturer: EDS srl - V. Cà Nova Zampieri 6 - 37057 S.G.
Lupatoto - Verona - ITALY
Power Supply: 12/24 Vdc
Power Supply Range: 11- 30 Vdc
Max Optical path:
120 m for RK100B
200 m for RK200B
Max cover area.: 1.600 sm (EN54-14 standard)
Protection against the inversion of polarity
Digitally codified infrared beam
Power Consumption of TX: 9,5 mA
Power Consumption of RX:
18,6 mA in normal operation
34 mA with the alarm relay activated
34 mA with the turbulence relay activated
50 mA with both alarm and fault relay activated
Maximum angular missallignment of the detector: +/- 0,5°
Selection of the obscuration alarm threshold level with a 4
positions switch:
position 1 - 70%
position 2 - 60%
position 3 - 50%
position 4 - 40%
Selection of the turbulence alarm threshold level with a 4 positions
switch
Alarm Relay activation delay: 10 s
Fault Relay activation delay: 5 s
Detector's recovery time with alarm memory dectivated: about
5 s
Detector's recovery time with alarm memory activated: about
5 s (power supply off)
Working temperature: -10 + 55°C
Red LED indication: alarm status
Blue LED indication: compensation limit, interrupted beam,
fault
Alarm Relay: 1A/24 V dc
Turbulence Relay: 1A/24 V dc
Fault/Maintenance Relay: 1A/24 V dc
0-5 V Analog Output for signal level measuring/visualization
Dimensions: 247 x 146 x 114 mm.
Housing: autoextinguishing policarbonate box
Relevant Standard: EN 54-12
Certifications: EN54-12/CPD (0786-CPD-20803), VDS2504-
VDS2344 (G209131)
Protection Index: IP 65 (IEC 529-144)
Weight: 900 gr.