EDS - RK90R - OPTICAL BEAM SMOKE DETECTOR - USER GUIDE
20
TECHNICAL DATA
• Models: RK100B, RK200B
• Type: Barrier Optical Beam Smoke Detector
• Manufacturer: EDS srl - V. Cà Nova Zampieri 6 - 37057 S.G. Lupatoto - Verona - ITALY
• Power Supply: 12/24 Vdc
• Power Supply Range: 11- 30 Vdc
• Max Optical path:
120 m for RK100B
200 m for RK200B
• Max cover area.: 1.600 sm (EN54-14 standard)
• Protection against the inversion of polarity
• Digitally codified infrared beam
• Power Consumption of TX: 9,5 mA
• Power Consumption of RX:
18,6 mA in normal operation
34 mA with the alarm relay activated
34 mA with the turbulence relay activated
50 mA with both alarm and fault relay activated
• Maximum angular missallignment of the detector: +/- 0,5°
• Selection of the obscuration alarm threshold level with a 4 positions switch:
position 1 - 70%
position 2 - 60%
position 3 - 50%
position 4 - 40%
• Selection of the turbulence alarm threshold level with a 4 positions switch
• Alarm Relay activation delay: 10 s
• Fault Relay activation delay: 5 s
• Detector's recovery time with alarm memory dectivated: about 5 s
• Detector's recovery time with alarm memory activated: about 5 s (power supply off)
• Working temperature: -10 + 55°C
• Red LED indication: alarm status
• Blue LED indication: compensation limit, interrupted beam, fault
• Alarm Relay: 1A/24 V dc
• Turbulence Relay: 1A/24 V dc
• Fault/Maintenance Relay: 1A/24 V dc
• 0-5 V Analog Output for signal level measuring/visualization
• Dimensions: 247 x 146 x 114 mm.
• Housing: autoextinguishing policarbonate box
• Relevant Standard: EN 54-12
• Certifications: EN54-12/CPD (0786-CPD-20803), VDS2504-VDS2344 (G209131)
• Protection Index: IP 65 (IEC 529-144)
• Weight: 900 gr.