RPS Cooling Requirements
– 19 –
Figure 7: RPS Cooling
Rack Cooling
When mounting the RPS in an enclosed rack or cabinet, be sure to check the following
guidelines to prevent overheating:
Make sure that enough cool air can flow into the enclosure for the equipment it
contains. The RPS requires 14 CFM of cooling air flow.
Check that the rack or cabinet allows the hot air to exit the enclosure (normally
from the top) without circulating back into equipment.
If the enclosure has sides or doors with ventilation holes, make sure they are not
blocked by cables or other obstructions.
Route cables within the rack or cabinet to maximize the airflow.
When possible, do not completely fill the rack or cabinet with equipment; allow
some unused space within the enclosure for better airflow.
Warm Air Cool Air