Specifications

Electric Latch Pullback - M94
Continuous-duty solenoid retracts the
latch bolt(s) for momentary or
maintained periods of time. Latch
Pullback provides a remote means of
unlocking exit devices.
Application
SecureBoltâ„¢ Exit Devices
Rim Exit Devices
Surface Vertical Rod Exit Devices
Concealed Vertical Rod Exit Devices
Mortise Exit Devices
Listings
UL listed for both Panic and Fire Exit
Hardware.
Electrical Specifications
Requires 781N Controller (120VAC
input, output sequencer for one or two
devices). No substitutes; using other
power sources voids warranty. Requires a
4-wire electrical transfer pivot or hinge.
Solenoid
A dual retraction/holder-type solenoid.
6-9 Amp in rush @ 24VDC to 28VDC
(.172 Amp holding-continuous duty.)
Device bolts remain retracted for as long
as the device is energized. Removal of
power returns the device to the life safety,
self-latching mechanical mode.
Interface with central or local fire alarm
system, automatic door operators, access
control systems, security alarm systems,
and blow open door systems.
Note: This feature is not available with
Electric Dogging (M97) on the same
device.
How to Order
Specify Quick Code M94.
Electric Dogging - M97
This electronic feature will provide
continuous dogging when power is
applied and the push bar is depressed
manually. Interruption or removal of the
power will release the pushbar and return
the exit device back to normal operation.
Application
SecureBoltâ„¢ Exit Devices
Rim Exit Devices
Surface Vertical Rod Exit Devices
Concealed Vertical Rod Exit Devices
Mortise Exit Devices
Listings
UL listed for both Panic and Fire Exit
Hardware.
Electrical Specifications
.35 Amps @ 24VDC continuous duty (2)
36 volt holding magnets holding force
(86 lbf. total)
Note: This feature is not available with
Electric Latch Pullback (M94) on the
same device.
How to Order
Specify Quick Code M97.
Mortise Device Trim Control
Safe or Secure
Mortise device trim control provides a
remote means of locking and unlocking
the outside lever trim. This feature is
provided by continuous duty solenoids in
the device mortise lock.
Application
Mortise Exit Devices
Listings
UL listed for both Panic and Fire Exit
Hardware.
Electrical Specifications
24VDC 330 milliamperes
Fail Safe units maintain the door locked
as long as the device is energized.
Fail Secure units maintain the door
unlocked as long as the device is
energized.
Regulated 24VDC power supply required.
Note: SAF & SEC options are only
available with ED5600L lock body
functions and may not be combined
with either the M91 or M93 monitoring
options.
How to Order
Specify Quick Code "SAF" for Safe or
"SEC" for Secure.
Electrified Exit Devices
ED5000.33
ED5000 Series Pushpad Exit Devices