Specifications
5
RG SERIES ENGINEERING GUIDE
AHRI Data
All RG Series product is safety listed under UL1995 thru ETL and performance listed with
AHRI in accordance with standard 13256-1.
P
SC
Motor
AHRI/ASHRAE/ISO 13256-1
English (IP) Units
Model
Flow Rate
Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump
Cooling
EWT 86°F
Heating
EWT 68°F
Cooling
EWT 59°F
Heating
EWT 50°F
Cooling
EWT 77°F
Heating
EWT 32°F
gpm cfm
Capacity
Btu/h
EER
Btu/h/W
Capacity
Btu/h
COP
Capacity
Btu/h
EER
Btu/h/W
Capacity
Btu/h
COP
Capacity
Btu/h
EER
Btu/h/W
Capacity
Btu/h
COP
009 3.0 350 8,500 12.0 11,500 4.4 10,500 18.2 9,600 3.7 9,100 13.5 7,600 3.0
012 3.5 400 10,900 12.7 14,700 4.4 12,500 18.2 12,000 3.8 11,500 14.7 9,600 3.2
015 4.0 500 14,000 15.0 16,500 4.8 16,000 24.0 15,000 4.1 14,700 17.2 11,500 3.5
018 5.0 600 17,600 14.6 21,000 4.7 20,600 23.5 17,500 4.0 18,500 17.0 13,700 3.5
023 6.0 800 23,000 14.5 26,000 4.5 25,400 22.5 21,900 3.9 23,900 16.8 17,000 3.4
024 6.0 800 23,900 14.6 27,000 4.7 26,400 22.8 22,300 4.0 24,400 17.0 17,500 3.5
030 8.0 1000 29,500 14.9 34,600 4.8 32,900 23.0 28,300 4.0 29,000 17.0 22,800 3.5
036 9.0 1150 33,300 14.4 40,600 4.5 37,700 21.2 33,000 3.9 34,500 16.6 26,000 3.3
041 11.0 1300 40,000 13.8 45,000 4.3 44,500 20.6 36,000 3.8 41,000 15.8 29,000 3.3
042 11.0 1400 40,800 14.5 45,400 4.5 45,800 22.0 37,000 3.8 42,300 16.8 29,900 3.3
048 12.0 1600 47,700 14.7 56,000 4.4 52,000 21.0 45,900 3.8 49,500 16.8 36,900 3.3
060 15.0 1900 58,400 14.7 72,500 4.4 65,500 20.8 58,400 3.8 60,900 16.6 47,100 3.3
070 18.0 2100 63,000 14.2 79,000 4.4 70,000 20.3 64,100 3.8 68,500 15.2 51,600 3.3
12/6/10
Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature
Heating capacities based upon 68°F DB, 59°F WB entering air temperature
All ratings based upon 208V operation
Variable Speed ECM, or 5-Speed ECM Motor
AHRI/ASHRAE/ISO 13256-1
English (IP) Units
Model
Flow Rate
Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump
Cooling
EWT 86°F
Heating
EWT 68°F
Cooling
EWT 59°F
Heating
EWT 50°F
Cooling
EWT 77°F
Heating
EWT 32°F
gpm cfm
Capacity
Btu/h
EER
Btu/h/W
Capacity
Btu/h
COP
Capacity
Btu/h
EER
Btu/h/W
Capacity
Btu/h
COP
Capacity
Btu/h
EER
Btu/h/W
Capacity
Btu/h
COP
015 4.0 500 14,000 15.3 16,500 4.9 16,000 24.3 15,000 4.4 14,700 17.5 11,500 3.7
018 5.0 600 17,600 15.2 21,000 4.8 20,600 24.0 17,500 4.4 18,500 17.5 13,700 3.7
023 6.0 800 23,000 15.0 26,000 4.7 25,400 23.0 21,900 4.3 23,900 17.0 17,000 3.6
024 6.0 800 23,900 15.1 27,000 5.0 26,400 23.4 22,300 4.5 24,400 17.5 17,500 3.8
030 8.0 900 29,500 15.7 34,600 5.1 32,900 23.9 28,300 4.4 29,000 18.3 22,800 3.8
036 9.0 1150 33,300 15.0 40,600 4.8 37,700 23.0 33,000 4.3 34,500 17.3 26,000 3.5
041 11.0 1300 40,000 14.5 45,000 4.5 44,500 22.0 36,000 4.0 41,000 16.5 29,000 3.4
042 11.0 1400 40,800 15.6 45,400 5.0 45,800 23.5 37,000 4.3 42,300 18.5 29,900 3.7
048 12.0 1600 47,700 15.5 56,000 4.8 52,000 23.4 45,900 4.2 49,500 18.1 36,900 3.6
060 15.0 1900 58,400 15.3 72,500 4.7 65,500 23.0 58,400 4.0 60,900 17.9 47,100 3.6
070 18.0 2100 63,000 14.3 79,000 4.7 70,000 21.0 64,100 4.0 68,500 16.1 51,600 3.5
12/6/10
Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature
Heating capacities based upon 68°F DB, 59°F WB entering air temperature
A
ll ratings based upon 208V operation