Specifications
44
RG SERIES ENGINEERING GUIDE
Blower Performance Data cont.
V
ariable
S
peed E
C
M Motor
Model
Max
esp
Airfl ow DIP Switch Settings
123456789101112
015 0.50
300 400 500 600 700
LMH
018 0.50
300 400 500 600 700 800
LMH
023 0.50
400 500 600 700 800 900 1000 1100 1200
LM H
024 0.50
400 500 600 700 800 900 1000 1100 1200
LM H
030 0.50
400 500 600 700 800 900 1000 1100 1200
LMH
036 0.50
600 700 800 900 1000 1100 1150 1225 1300
LM H
041 0.50
650 750 850 950 1050 1150 1250 1325 1375 1475 1550 1600
LM H
042 0.50
650 750 850 950 1050 1150 1250 1325 1375 1475 1550 1600
LM H
042
w/1hp*
0.75
800 1000 1100 1300 1500 1600 1800
LM H
048 0.50
650 750 850 950 1050 1150 1250 1325 1375 1475 1550 1600
LM H
048
w/1hp*
0.75
800 1000 1100 1300 1500 1600 1800
LMH
060 0.75
750 900 1000 1200 1400 1600 1700 1850 2000 2200 2300 2400
LM H
070 0.75
800 950 1100 1300 1500 1750 1950 2100 2300
LMH
11/10/09
Factory settings are at recommended L-M-H DIP switch locations.
Shaded regions are recommended for best performance. It is acceptable to operate outside of this area as long as the WSHP operates within the guidlines of the Oper-
ating Limits table and Correction Factor tables.
Lowest and Highest DIP switch settings are assumed to be L and H respectively.
CFM is controlled within ±5% up to the maximum esp.
Max esp includes allowance for wet coil and standard fi lter