RG Series Engineering Guide RG Series Commercial Geothermal/Water Source Heat Pump • R-410A Refrigerant • 0.75-6 Ton Design Features Factory Options Accessories Dimensional Data Physical Data Performance Data Engineering Guide Specifications Form: 146.00-EG1A (1013) Supercedes: 146.
RG SERIES ENGINEERING GUIDE Table of Contents Model Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 AHRI Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6 The RG Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RG SERIES ENGINEERING GUIDE Model Nomenclature 1-2 3 4 5-7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22-23 24 RG S V 036 T L 0 0 0 C A N N A 5 N 0 0 SS * Model Type RG – RG Series Vintage * - Factory Use Only Operation Range S – Single Stage Non-Standard Options SS – Standard Cabinet Configuration V – Vertical H - Horizontal Drain Pan Option 0 – Composite, No Secondary Connection 1 – Composite, Secondary Connection 2 – Stainless Steel, No Secondary Connection 3 – St
RG SERIES ENGINEERING GUIDE AHRI Data PSC Motor AHRI/ASHRAE/ISO 13256-1 English (IP) Units Water Loop Heat Pump Flow Rate Model Cooling EWT 86°F Capacity Btu/h EER Btu/h/W Ground Water Heat Pump Heating EWT 68°F Capacity Btu/h COP Cooling EWT 59°F Capacity Btu/h EER Btu/h/W Ground Loop Heat Pump Heating EWT 50°F Capacity Btu/h COP Cooling EWT 77°F Capacity Btu/h EER Btu/h/W Heating EWT 32°F Capacity Btu/h gpm cfm COP 009 3.0 350 8,500 12.0 11,500 4.4 10,500 18.2 9,600 3.
RG SERIES ENGINEERING GUIDE AHRI Data cont. The performance standard AHRI/ASHRAE/ISO 13256-1 became effective January 1, 2000 and replaces AHRI Standards 320, 325, and 330. This new standard has three major categories: Water Loop (comparable to ARI 320), Ground Water (ARI 325), and Ground Loop (ARI 330). Although these standards are similar there are some differences: Unit of Measure: The Cooling COP The cooling efficiency is measured in EER (US version measured in Btu/h per Watt.
RG SERIES ENGINEERING GUIDE The RG Series The RG Series represents a significant improvement in the commercial water source heat pump (wshp). The R-410A product features high efficiency with industry leading standard options in a compact cabinet suitable for both retrofit and new construction applications. The product is also targeted to provide optimum performance and flexibility in both water loop and geothermal applications.
RG SERIES ENGINEERING GUIDE The RG Series cont. Product Features: Vertical Cabinet RG Series vertical units are designed for high efficiency, maximum flexibility, and primary servicing from the front. Standard filter rail, field switchable for 1 in. or 2 in. filters Optional factory mounted deluxe filter rack (shown), field switchable for 1 in. or 2 in.
RG SERIES ENGINEERING GUIDE The RG Series cont. Product Features: Horizontal Cabinet RG Series horizontal units are available in seven cabinet sizes. The cabinets are designed for high efficiency, maximum flexibility, and primary servicing from the front. NEW!: Oversized rifled tube/ lanced fin all-aluminum air coil (optional AlumiSeal coating).
RG SERIES ENGINEERING GUIDE The RG Series cont. Flexible Product with Several Standard Options Super Quiet Option • Compact cabinet design, vertical and horizontal with true left and right return configurations • Horizontal end and side discharge with vertical top discharge air configurations • Capacities of 9,000 through 70,000 Btu/h • All commercial voltages including 208-230/60/1, 265-277/60/1, 208-230/60/3, 460/60/3, and 575/60/3.
RG SERIES ENGINEERING GUIDE The RG Series cont. Aurora Base Control FX10 Control The Aurora Base Control (ABC) System is a complete residential and commercial comfort system that brings all aspects of the HVAC system into one cohesive module network. Aurora uses the Modbus communication protocol to communicate between modules. Each module contains the logic to control all features that are connected to the module. The Aurora Base Control (ABC) has two Modbus channels.
RG SERIES ENGINEERING GUIDE The RG Series cont. Internally Mounted Solenoid Valve Option Phase Guard Monitor When variable speed circulating pump systems are designed, low pressure drop (high Cv) solenoid valves are specified at each unit to vary the pump according to flow required. It is important that these valves be low pressure drop to avoid unwanted pump watts. This option factory installs this valve inside the unit.
RG SERIES ENGINEERING GUIDE Inside the RG Series cont. feature an internally trapped condensate line using clear PVC hose for easy inspection and reduced installation cost. Optional factory installed stainless steel drain pans are also available. flexibility. A MERV 4, 1 in. [2.54 cm] is standard with an optional 2 in. [5.1 cm] MERV 13 for LEED certification points and high efficiency filtration. Compressors High efficiency R-410A rotary or scroll compressors are used on every model.
RG SERIES ENGINEERING GUIDE Inside the RG Series cont. the motor for easy speed change. All motors are vibration isolated to reduce noise. High static options are available in some models for both PSC and variable speed ECM motor versions. Horizontal units can be field converted from end to side discharge as well. Water-to-Refrigerant Coaxial Heat Exchanger Coil Large oversized coaxial refrigerant to water heat exchangers provide unparalleled efficiency.
RG SERIES ENGINEERING GUIDE Controls - Aurora Base Controls Aurora ‘Base’ Control Field Selectable Options via Hardware DIP Switch (SW1) – Test/Configuration Button (See SW1 Operation Table) Test Mode The control is placed in the test mode by holding the push button switch SW1 for 2 - 5 seconds. In test mode most of the control timings will be shortened by a factor of sixteen (16). LED3 (green) will flash at 1 second on and 1 second off.
RG SERIES ENGINEERING GUIDE Controls - Aurora Base Controls cont. Cycle with Blower - The accessory relay will cycle with the blower output. Lockout – when locked out, the blower will operate continuously in “G” speed, and PSC blower motor output will remain on. The Alarm output (ALM) and Lockout output (L) will be turned on. The fault type identification display LED1 (Red) shall flash the fault code.
RG SERIES ENGINEERING GUIDE Controls - Aurora Base Controls cont. Over/Under Voltage Shutdown - An over/under voltage condition exists when the control voltage is outside the range of 18 VAC to 30 VAC. If the over/under voltage shutdown lasts for 15 minutes, the lockout and alarm relay will be energized. Over/under voltage shutdown is self-resetting in that if the voltage comes back within range of 18 VAC to 30 VAC for at least 0.5 seconds, then normal operation is restored.
RG SERIES ENGINEERING GUIDE Controls - Aurora Base Controls cont. Aurora ‘Base’ Control LED Displays Aurora Interface and Diagnostics (AID) Tool These three LEDs display the status, configuration, and fault codes for the control. These can also be read in plain English via the Aurora AID Tool. The Aurora Interface and Diagnostics (AID) Tool is a device that is a member of the Aurora network. The AID Tool is used to troubleshoot equipment which uses the Aurora control via Modbus RTU communication.
RG SERIES ENGINEERING GUIDE Controls - FX10 (optional) An optional Medium User Interface (MUI) for control setup and advanced diagnostics is available with some mounting kits, MUIK3 - Panel mount version and the MUIK4-Wall mount version. Optional FX10 Microprocessor and BAS Interface Zone Sensors There are two options for zone sensors that can be used with the FX10 control. Both sensors use a Johnson controls A99 positive temperature coefficient type sensor.
RG SERIES ENGINEERING GUIDE Controls - FX10 (optional) cont. checked 15 seconds before compressor start up to be sure the pressure switch is closed and then ignored for the first 2 minutes after the compressor output (BO-2) is enabled. If the switch is open continuously for (30) seconds during compressor operation the compressor output (BO-2) will be disabled. The compressor will not restart until the compressor short cycle time delay has been satisfied.
RG SERIES ENGINEERING GUIDE Controls - FX10 (optional) cont. Set Point Control Mode In set point control mode the reversing valve output will be enabled. As the temperature falls below the cooling set point and begins to operate in the cooling proportional band, the low capacity compressor output (BO-2) will be enabled. A PI loop in the programming of the control will determine when the full capacity compressor output (BO-4) is to be enabled.
RG SERIES ENGINEERING GUIDE Controls - FX10 (optional) cont. Emergency Heat/Network Enabled Output (BO5) Inputs and Outputs Configuration This output is set from the factory to enable/disable emergency heat. If a problem occurs with the unit resulting in the compressor being locked out in heating mode, the control will automatically enable this output to turn on field installed electric heat.
RG SERIES ENGINEERING GUIDE Hot Gas Reheat Dehumidification Overview Hot Gas Reheat Dehumidification Overview Dehumidification - The Need for Reheat With tighter construction and more and more ventilation air being introduced into buildings, there is more need now than ever for proper humidity control. Ensuring dehumidification can provide consistent employee comfort, a reduction in mold liability, a reduction in cooling costs.
RG SERIES ENGINEERING GUIDE Hot Gas Reheat Dehumidification Overview cont. Hot Gas Reheat Dehumidification Overview cont. Variable speed ECM models will generally compensate up to their maximum ESP of 0.5 in. wg. for 1/2 hp and 0.75 in. wg. for 1 hp. Btu/hr may be converted to lbs/hr or grains per hour as shown in the equations below. Model VS048, 1500 cfm, H x W = SA 20 x 40 = 800 in.2 = 5.56 ft.2 11,900 Btu/h / 1,069 Btu/lb of water vapor at 80/67 DB/WB°F = 11.
RG SERIES ENGINEERING GUIDE Hot Gas Reheat - Controls The reheat option is available with the Aurora or FX10 control. Three control schemes are available: Dehumidification Mode Operation Upon a call for dehumidification, the blower relay and reversing valve coil are energized immediately, and the compressor contactor will energize after a 90 second delay. The reheat valve coil will energize once the compressor has been operational for 30 seconds.
RG SERIES ENGINEERING GUIDE Application Notes on individual units without system shut-down. Conditions remain comfortable since each unit operates separately, allowing cooling in one area and heating in another. Tenant spaces can be finished and added as needed. Power billing to tenants is also convenient since each unit can be individually metered: each pays for what each uses. Nighttime and/or weekend uses of certain areas are possible without heating or cooling the entire facility.
RG SERIES ENGINEERING GUIDE Application Notes cont. Because auxiliary equipment such as a fossil fuel boiler and cooling tower are not required to maintain the loop temperature, operating and maintenance costs are very low. surface run-off. Sizing requirements for the surface water is a minimum of 500 sq. ft./ton of surface area at a minimum depth of 8 feet. Your sales representative should be contacted when designs for heating dominated structures are required.
RG SERIES ENGINEERING GUIDE Application Notes cont. • Closed Loop /Cooler-Boiler Systems utilize a closed heat recovering loop with multiple water source heat pumps in the more conventional manner. Typically a boiler is employed to maintain closed loop temperatures above 60°F and a cooling tower to maintain loop temperatures below 90°F. These systems are applicable in medium to large buildings regardless of whether the load is heating or cooling dominated.
RG SERIES ENGINEERING GUIDE Installation Notes is typically stainless steel braid and includes a swivel fitting on one end for easy removal and is flexible to help isolate the unit for quieter operation. Isolation valves for servicing, y-strainers for filtering and memory-stop flow valve or a balancing valve can be provided for consistent water flow through the unit. Typical Unit Installation Unit Location Locate the unit in an indoor area that allows for easy removal of the filter and access panels.
RG SERIES ENGINEERING GUIDE Installation Notes cont. directions to facilitate the removal of condensate. Use only the bolts provided in the kit to attach hanger brackets. The use of longer bolts could damage internal parts. Installing Horizontal Units Remove and discard the compressor hold down shipping bolt located at the front of the compressor mounting bracket prior to setting the unit in place. Horizontal units are available with side or end discharge.
RG SERIES ENGINEERING GUIDE Installation Notes cont. Ductwork • Ensure return air grilles will not allow line of site noise to transfer to adjacent space. Use a sound barrier or some other material to isolate the grille from the unit. A supply grille, boot and short piece of flex duct pointed away from the unit can greatly attenuate equipment noise. • Use a canvas isolation duct connector at the supply and return duct connection of the unit.
RG SERIES ENGINEERING GUIDE Vertical Dimensional Data Standard filter rails for open return applications Field installed duct flange Deluxe filter rack for ductable return applications A A N S R Air coil N Q P B AIR COIL SIDE AIR COIL SIDE Q P 4 G 3 F ACCESS PANEL B 2' (61 cm) Alternate Service Access 4 FRONT FRONT 1.4 in (3.5 cm) M G 3 F 1.4 in (3.
RG SERIES ENGINEERING GUIDE Vertical Dimensional Data cont. Overall Cabinet Vertical Models 009-012 015-018 024-030 036 041 042-048 060 070 A in. cm. in. cm. in. cm. in. cm. in. cm. in. cm. in. cm. in. cm. Vertical Models 009-012 015-018 024-030 036 041 042-048 060 070 in. cm. in. cm. in. cm. in. cm. in. cm. in. cm. in. cm. in. cm. B C 1 2 3 D E F Width Depth Height** In Out 22.5 57.2 22.5 57.2 22.5 57.2 22.5 57.2 22.5 57.2 25.5 64.8 25.5 64.8 25.5 64.8 22.2 56.4 22.2 56.4 26.2 66.
RG SERIES ENGINEERING GUIDE Horizontal Dimensional Data 1.7 in. [5.3 cm] Standard filter rails 1 in. [2.5 cm] knockout 0.5 in. [1.3 cm] knockout Front Right Return 1.7 in. [5.3 cm] Standard filter rails K CP Left Return Front AP J E A AP D AP RR Front View CMP CMP 1.7 1.7 2' (61 cm) Service Access Condensate "X" PVC size AP E Deluxe filter rack option shown 2.3 in. [5.8 cm] P N D K Side Discharge 1 in. [2.
RG SERIES ENGINEERING GUIDE Horizontal Dimensional Data cont. Water Connections 2 3 E H CondOut ensate 4.8 0.8 12.2 2.0 6.8 0.8 17.3 2.0 6.8 0.8 17.3 2.0 6.8 0.8 17.3 2.0 6.8 0.8 17.3 2.0 6.8 0.8 17.3 2.0 6.8 0.8 17.3 2.0 Overall Cabinet Horizontal Models 009-012 015-023 024-030 036 042-048 060 070 in. cm. in. cm. in. cm. in. cm. in. cm. in. cm. in. cm. Horizontal Models 009-012 015-023 024-030 036 042-048 060 070 A B C 1 D Width Depth Height* In 19.2 48.8 22.5 57.2 22.5 57.2 22.5 57.2 25.
RG SERIES ENGINEERING GUIDE Hanger Bracket Locations Right D Left F Compressor Section E G Air Handler Section C B Air Handler Section E G D Compressor Section F A 3/8” Threaded Rod (not supplied) Vibration Isolator Washer Hex Nuts (not supplied) Bolt and Lockwasher Hanger Dimensions Hanger Kit Part Number Model 009-012 015-023 024-030 036 042-048 060 070 in. cm in. cm in. cm in. cm in. cm in. cm in.
RG SERIES ENGINEERING GUIDE Physical Data Single Speed Model 009 012 Compressor (1 each) 015 018 023 024 030 036 041 Rotary 042 048 060 070 Scroll Factory Charge R-410A, oz [kg] Vertical 26 [0.74] 32 [0.91] 38 [1.08] 40 [1.13] n/a 46 [1.30] 54 [1.53] 56 [1.59] 54 [1.53] 68 [1.93] 76 [2.15] 88 [2.49] 92 [2.61] Factory Charge R-410A, oz [kg] Horizontal 24 [0.68] 26 [0.74] 38 [1.08] 40 [1.13] 46 [1.30] 46 [1.30] 56 [1.59] 60 [1.70] n/a 68 [1.93] 76 [2.15] 88 [2.
RG SERIES ENGINEERING GUIDE Electrical Availability PSC Voltage Static Option 208-230/60/1 Single Speed Models 009 012 015 018 023 024 030 036 041 042 048 060 070 • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • 208-230/60/1 w/GeoStart 265-277/60/1 208-230/60/3 (also w/GeoStart) Standard • • • 460/60/3 (also w/GeoStart) 575/60/3 208-230/60/1 • • • • 208-230/60/1 w/GeoStart • • •
RG SERIES ENGINEERING GUIDE Electrical Data PSC Motor Model 009 012 015 018 023 024 024* 030 030* 036 041 042 042* 048 048* 060 070 LRA** Blower Motor FLA Total Unit FLA Min Circ Amp Max Fuse/ HACR n/a n/a n/a n/a n/a n/a 13.4 n/a 23.3 n/a 33.0 16.8 23.3 n/a 33.0 16.8 23.3 n/a 33.0 16.8 29.2 n/a 34.8 16.8 29.2 n/a 34.8 16.8 38.7 n/a 57.0 27.0 46.0 57.0 27.0 n/a 46.0 57.0 27.0 n/a 46.0 57.0 27.0 n/a 46.0 69.0 30.0 46.0 69.0 30.0 n/a 60.0 72.0 42.0 n/a 58.0 72.0 42.0 n/a 0.6 0.6 0.6 0.
RG SERIES ENGINEERING GUIDE Electrical Data cont.
RG SERIES ENGINEERING GUIDE Electrical Data cont.
RG SERIES ENGINEERING GUIDE Blower Performance Data Standard PSC Motor Model 009 012 015 018 023 024 030 036 041 042 048 060 070 Blower Spd H MH ML* L H MH* ML L H M L H M L H M L H M L H M L H M L H M L H M L H M L H M L H M L Blower Size Motor hp 6x8 1/10 6x8 1/10 9x7 1/6 9x7 1/6 9x7 1/5 9x7 1/5 9x7 1/3 9x7 1/2 10x10 1/2 10 x 10 1/2 10 x 10 1/2 11 x 10 1 11 x 10 1 0 530 475 435 370 530 475 435 370 875 760 630 875 760 630 1020 960 720 1065 880 805 1240 1095 860 1
RG SERIES ENGINEERING GUIDE Blower Performance Data cont.
RG SERIES ENGINEERING GUIDE Blower Performance Data cont. Variable Speed ECM Motor Model Max esp 015 0.50 018 0.50 023 0.50 024 0.50 030 0.50 036 0.50 041 0.50 042 0.50 042 w/1hp* 0.75 048 0.50 048 w/1hp* 0.75 060 0.75 070 0.
RG SERIES ENGINEERING GUIDE Blower Performance Data cont. Setting Blower Speed - Variable Speed ECM Variable Speed ECM Setup with an AID Tool cont. The ABC board’s Yellow Config LED will flash the current variable speed ECM blower speed selections for low, med, and high continuously with a short pause in between. The speeds can also be confirmed with the AID Tool under the Setup/ECM Setup screen. The variable speed ECM blower motor speeds can be field adjusted with or without using an AID Tool.
RG SERIES ENGINEERING GUIDE Selection Example To achieve optimal performance, proper selection of each heat pump is essential. A building load program should be used to determine the heating and cooling load of each zone. A computer software selection program can then be used to develop an accurate and complete heat pump schedule. Software can be obtained from your local commercial representative. Step 4: Enter tables at the design water flow and water temperature.
RG SERIES ENGINEERING GUIDE Selection Example cont. 3, 4 & 5. HP Selection: HR = 500 x gpm x (Tin - Tout) HR = (Tin - Tout) or ¨T Rise 500 x gpm After making our preliminary selection (US*060 ECM), we enter the tables at design water flow and water temperature and read Total Cooling, Sens. Cooling and Heat of Rej. capacities: Total Cooling ..............................................................60,500 Btu/h Sensible Cooling........................................................
RG SERIES ENGINEERING GUIDE Reference Calculations Heating Calculations: LWT = EWT - HE GPM x 500 LAT = EAT + HC CFM x 1.08 Cooling Calculations: LWT = EWT + HR GPM x 500 LAT (DB) = EAT (DB) - SC CFM x 1.
RG SERIES ENGINEERING GUIDE Operating Limits Cooling Operating Limits Air Limits Min. Ambient Air Rated Ambient Air Max. Ambient Air Min. Entering Air Rated Entering Air db/wb Max. Entering Air db/wb Water Limits Min. Entering Water Normal Entering Water Max. Entering Water Heating (°F) (°C) (°F) (°C) 45 80 100 50 80.6/66.2 110/83 7.2 26.7 37.8 10.0 27/19 43/28.3 45 70 85 40 68 80 7.2 21.1 29.4 4.4 20.0 26.7 30 50-110 120 -1.1 10-43.3 48.9 20 30-70 90 -6.7 -1.1 32.
RG SERIES ENGINEERING GUIDE Pressure Drop Model 009 012 015 018 023 024 030 036 041 042 048 060 070 gpm Pressure Drop (psi) Cv 1.0 1.5 9.6 0.02 1.8 2.0 9.7 0.04 3.0 9.9 0.09 6.0 4.0 10.1 0.16 0.8 0.7 1.5 9.6 0.02 1.8 1.5 2.5 9.8 0.06 3.2 2.7 2.3 3.5 10.0 0.12 4.9 4.5 3.8 3.5 4.5 10.2 0.19 0.5 0.5 0.4 0.4 2.0 9.7 0.04 1.1 1.0 0.9 0.8 0.6 3.0 9.9 0.09 4.0 1.9 1.8 1.6 1.5 1.3 4.0 10.1 0.16 5.0 3.3 3.2 3.0 2.9 2.7 5.0 10.
RG SERIES ENGINEERING GUIDE RGS009 - Performance Data Single Speed PSC (350 cfm) WPD EWT °F 20 30 40 50 60 70 80 90 100 110 120 HEATING - EAT 70°F COOLING - EAT 80/67°F Flow gpm psi ft. hd. 1.5 2.2 5.1 2.0 4.2 9.7 3.0 7.5 17.3 1.5 2.0 4.6 2.0 3.8 8.8 6.1 0.64 3.9 84.1 2.79 11.2 7.5 0.67 0.52 13.0 21.7 3.0 7.2 16.6 6.9 0.67 4.6 86.2 3.01 11.4 7.7 0.67 0.49 13.0 23.4 1.5 1.9 4.4 2.0 3.5 8.1 6.9 0.67 4.6 86.3 3.03 11.1 7.6 0.68 0.55 13.
RG SERIES ENGINEERING GUIDE RGS012 - Performance Data Single Speed PSC (400 cfm) WPD EWT °F 20 30 40 50 60 70 80 90 100 110 120 HEATING - EAT 70°F COOLING - EAT 80/67°F Flow gpm psi ft. hd. 1.5 1.2 2.8 2.5 2.6 6.0 3.5 4.1 9.5 1.5 1.1 2.5 2.5 2.5 5.8 8.6 0.81 5.9 88.0 3.13 15.7 10.0 0.64 0.47 17.3 33.5 3.5 3.9 9.0 8.9 0.83 6.1 88.6 3.14 15.9 10.2 0.64 0.44 17.4 36.1 1.5 1.1 2.4 2.5 2.4 5.5 9.6 0.83 6.8 90.2 3.39 15.3 10.0 0.65 0.53 17.
RG SERIES ENGINEERING GUIDE RGS015 - Performance Data Single Speed PSC (500 cfm) WPD HEATING - EAT 70°F EWT °F Flow gpm 2.0 0.6 1.4 20 3.0 1.2 2.8 4.0 2.0 4.6 2.0 0.6 1.4 3.0 1.1 4.0 30 40 50 60 70 80 90 100 110 120 psi ft. hd. HC MBtu/h Power kW HE MBtu/h LAT °F COOLING - EAT 80/67°F COP HWC TC SC MBtu/h MBtu/h MBtu/h Operation not recommended 6.6 86.5 2.93 S/T Ratio Power kW HR MBtu/h EER HWC MBtu/h Operation not recommended 10.0 1.00 1.2 2.6 11.0 1.
RG SERIES ENGINEERING GUIDE RGS018 - Performance Data Single Speed PSC (600 cfm) WPD HEATING - EAT 70°F EWT °F Flow gpm 3.0 1.2 2.8 20 4.0 2.0 4.6 5.0 3.4 7.8 3.0 1.1 2.6 4.0 1.9 5.0 30 40 50 60 70 80 90 100 110 120 psi ft. hd. HC MBtu/h Power kW HE MBtu/h LAT °F COOLING - EAT 80/67°F COP HWC TC SC MBtu/h MBtu/h MBtu/h Operation not recommended 8.9 88.1 3.15 S/T Ratio Power kW HR MBtu/h EER HWC MBtu/h Operation not recommended 13.0 1.21 1.4 4.4 14.5 1.
RG SERIES ENGINEERING GUIDE RGS023 - Performance Data Single Speed PSC (700 cfm) WPD EWT °F 20 30 40 50 60 70 80 90 100 110 120 HEATING - EAT 70°F COOLING - EAT 80/67°F Flow gpm psi ft. hd. 3.0 1.2 2.8 4.5 2.4 5.6 6.0 4.6 10.6 3.0 1.1 2.6 4.5 2.4 5.5 17.9 1.74 11.9 88.7 3.01 26.3 16.7 0.63 1.11 30.1 23.8 6.0 4.5 10.5 18.2 1.76 12.2 89.1 3.04 26.7 17.0 0.64 1.04 30.2 25.7 3.0 1.1 2.5 4.5 2.3 5.3 19.6 1.78 13.6 90.7 3.24 26.5 17.0 0.64 1.
RG SERIES ENGINEERING GUIDE RGS024 - Performance Data Single Speed PSC (800 cfm) WPD HEATING - EAT 70°F EWT °F Flow gpm 3.0 1.2 2.8 20 4.5 2.4 5.6 6.0 4.6 10.6 3.0 1.1 2.6 4.5 2.4 6.0 30 40 50 60 70 80 90 100 110 120 psi ft. hd. HC MBtu/h Power kW HE MBtu/h LAT °F COOLING - EAT 80/67°F COP HWC TC SC MBtu/h MBtu/h MBtu/h Operation not recommended 9.8 86.0 2.72 S/T Ratio Power kW HR MBtu/h EER HWC MBtu/h Operation not recommended 15.6 1.68 1.6 5.5 18.7 1.
RG SERIES ENGINEERING GUIDE RGS030 - Performance Data Single Speed PSC (1000 cfm) WPD EWT °F 20 30 40 50 60 70 80 90 100 110 120 HEATING - EAT 70°F COOLING - EAT 80/67°F Flow gpm PSI FT 4.0 1.0 2.2 6.0 1.9 4.5 8.0 3.8 8.7 4.0 0.9 2.1 6.0 1.9 4.4 21.2 1.96 14.5 87.6 3.16 2.1 30.4 19.3 0.64 1.38 8.0 3.7 8.5 22.0 1.98 15.2 88.4 3.26 2.1 30.8 19.7 0.64 1.30 4.0 0.9 2.0 6.0 1.8 4.3 23.9 2.00 17.1 90.1 3.50 2.3 31.3 20.2 0.64 1.41 8.0 3.
RG SERIES ENGINEERING GUIDE RGS036 - Performance Data Single Speed PSC (1250 cfm) WPD EWT °F 20 30 40 50 60 70 80 90 100 110 120 HEATING - EAT 70°F COOLING - EAT 80/67°F Flow gpm psi ft. hd. 5.0 1.5 3.4 7.0 2.6 6.0 9.0 6.1 14.1 5.0 1.4 3.1 7.0 2.5 5.8 27.4 2.46 19.0 90.1 3.27 2.5 35.9 25.1 0.70 1.64 41.5 21.9 --- 9.0 6.0 13.8 28.2 2.51 19.6 90.7 3.29 2.6 36.4 25.6 0.70 1.54 41.7 23.6 --- 5.0 1.3 2.9 7.0 2.4 5.5 30.8 2.52 22.2 92.8 3.
RG SERIES ENGINEERING GUIDE RGS041 - Performance Data Single Speed PSC (1300 cfm) WPD EWT °F 20 30 40 50 60 70 80 90 100 110 120 HEATING - EAT 70°F COOLING - EAT 80/67°F Flow gpm psi ft. hd 5.0 1.6 3.8 8.0 3.6 8.2 11.0 8.0 18.5 5.0 1.5 3.4 8.0 3.4 7.8 28.5 2.82 18.9 86.9 2.97 3.7 41.9 30.4 0.73 1.93 48.4 21.7 --- 11.0 7.9 18.1 29.5 2.86 19.7 87.5 3.02 3.8 42.4 31.0 0.73 1.81 48.6 23.4 --- 5.0 1.3 3.0 8.0 3.2 7.5 31.7 2.88 21.9 89.0 3.
RG SERIES ENGINEERING GUIDE RGS042 - Performance Data Single Speed PSC (1400 cfm) WPD EWT °F 20 30 40 50 60 70 80 90 100 110 120 HEATING - EAT 70°F Flow gpm psi ft. hd. 5.0 1.6 3.8 8.0 3.6 8.2 11.0 8.0 18.5 5.0 1.5 3.4 8.0 3.4 11.0 5.0 HC MBtu/h Power kW HE MBtu/h LAT °F COOLING - EAT 80/67°F COP HWC TC SC MBtu/h MBtu/h MBtu/h Operation not recommended 17.4 85.9 2.82 S/T Ratio Power kW HR MBtu/h EER HWC MBtu/h Operation not recommended 27.0 2.81 3.5 7.8 30.
RG SERIES ENGINEERING GUIDE RGS048 - Performance Data Single Speed PSC (1600 cfm) WPD EWT °F 20 30 40 50 60 70 80 90 100 110 120 HEATING - EAT 70°F Flow gpm psi 6.0 2.2 5.1 9.0 4.4 10.0 12.0 6.8 15.8 6.0 2.0 4.7 9.0 4.2 12.0 6.0 ft. hd. HC MBtu/h Power kW HE MBtu/h LAT °F COOLING - EAT 80/67°F COP HWC TC SC MBtu/h MBtu/h MBtu/h Operation not recommended 19.5 87.0 2.72 S/T Ratio Power kW HR MBtu/h EER HWC MBtu/h Operation not recommended 30.8 3.32 4.6 9.
RG SERIES ENGINEERING GUIDE RGS060 - Performance Data Single Speed PSC (2000 cfm) WPD HEATING - EAT 70°F COOLING - EAT 80/67°F EWT °F Flow gpm 9.0 3.8 8.7 20 12.0 6.3 14.5 15.0 9.7 22.5 9.0 3.6 8.4 12.0 6.1 14.1 43.8 3.99 30.2 88.3 3.22 5.9 72.0 49.1 0.68 2.96 82.1 24.3 --- 15.0 9.6 22.2 46.5 4.11 32.5 89.5 3.31 6.1 73.0 50.0 0.68 2.78 82.5 26.3 --- 30 40 50 60 70 80 90 100 110 120 psi ft. hd.
RG SERIES ENGINEERING GUIDE RGS070 - Performance Data Single Speed PSC (2200 cfm) WPD HEATING - EAT 70°F EWT °F Flow gpm 12.0 4.3 9.8 20 15.0 5.6 13.0 18.0 9.0 20.8 12.0 4.1 9.4 15.0 5.9 18.0 8.8 12.0 3.8 8.8 15.0 5.2 18.0 30 40 50 60 70 80 90 100 110 120 psi ft. hd. HC MBtu/h Power kW HE MBtu/h LAT °F COOLING - EAT 80/67°F COP HWC TC SC MBtu/h MBtu/h MBtu/h Operation not recommended 29.0 87.4 2.
RG SERIES ENGINEERING GUIDE RGS015 - Performance Data Single Speed Variable Speed ECM or 5-Speed ECM (500 cfm) WPD EWT °F 20 30 40 50 60 70 80 90 100 110 120 HEATING - EAT 70°F Flow gpm psi ft. hd. 2.0 0.6 1.4 3.0 1.2 2.8 4.0 2.0 4.6 2.0 0.6 1.4 3.0 1.1 4.0 HC MBtu/h Power kW HE MBtu/h LAT °F COOLING - EAT 80/67°F COP HWC TC SC MBtu/h MBtu/h MBtu/h Operation not recommended 6.8 86.5 3.09 S/T Ratio Power kW HR MBtu/h EER HWC MBtu/h Operation not recommended 10.
RG SERIES ENGINEERING GUIDE RGS018 - Performance Data Single Speed Variable Speed ECM or 5-Speed ECM (600 cfm) WPD EWT °F 20 30 40 50 60 70 80 90 100 110 120 HEATING - EAT 70°F Flow gpm psi ft. hd. 3.0 1.2 2.8 4.0 2.0 4.6 5.0 3.4 7.8 3.0 1.1 2.6 4.0 1.9 5.0 3.0 HC MBtu/h Power kW HE MBtu/h LAT °F COOLING - EAT 80/67°F COP HWC TC SC MBtu/h MBtu/h MBtu/h Operation not recommended 9.1 88.1 3.
RG SERIES ENGINEERING GUIDE RGS023 - Performance Data Single Speed Variable Speed ECM or 5-Speed ECM (800 cfm) WPD EWT °F 20 30 40 50 60 70 80 90 100 110 120 HEATING - EAT 70°F COOLING - EAT 80/67°F Flow gpm psi ft. hd. 3.0 1.2 2.8 4.5 2.4 5.6 6.0 4.6 10.6 3.0 1.1 2.6 4.5 2.4 5.5 17.9 1.59 12.4 88.7 3.29 26.3 16.7 0.63 0.94 29.6 27.9 6.0 4.5 10.5 18.2 1.61 12.7 89.1 3.31 26.7 17.0 0.64 0.89 29.7 30.2 3.0 1.1 2.5 4.5 2.3 5.3 19.6 1.63 14.
RG SERIES ENGINEERING GUIDE RGS024 - Performance Data Single Speed Variable Speed ECM or 5-Speed ECM (800 cfm) WPD EWT °F 20 30 40 50 60 70 80 90 100 110 120 HEATING - EAT 70°F COOLING - EAT 80/67°F Flow gpm psi ft. hd. 3.0 1.2 2.8 4.5 2.4 5.6 6.0 4.6 10.6 3.0 1.1 2.6 4.5 2.4 5.5 18.7 1.59 13.2 89.6 3.44 1.7 27.5 17.4 0.63 0.94 30.7 29.1 --- 6.0 4.5 10.5 19.0 1.61 13.5 90.0 3.46 1.7 27.8 17.7 0.64 0.89 30.9 31.5 --- 3.0 1.1 2.5 4.5 2.3 5.
RG SERIES ENGINEERING GUIDE RGS030 - Performance Data Single Speed Variable Speed ECM or 5-Speed ECM (1000 cfm) WPD EWT °F 20 30 40 50 60 70 80 90 100 110 120 HEATING - EAT 70°F Flow gpm psi ft. hd. 4.0 1.0 2.2 6.0 1.9 4.5 8.0 3.8 8.7 4.0 0.9 2.1 6.0 1.9 8.0 HC MBtu/h Power kW HE MBtu/h LAT °F COOLING - EAT 80/67°F COP HWC TC SC MBtu/h MBtu/h MBtu/h Operation not recommended 14.2 86.5 3.
RG SERIES ENGINEERING GUIDE RGS036 - Performance Data Single Speed Variable Speed ECM or 5-Speed ECM (1150 cfm) WPD EWT °F 20 30 40 50 60 70 80 90 100 110 120 HEATING - EAT 70°F Flow gpm psi ft. hd. 5.0 1.5 3.4 7.0 2.6 6.0 9.0 6.1 14.1 5.0 1.4 3.1 7.0 2.5 9.0 5.0 HC MBtu/h Power kW HE MBtu/h LAT °F COOLING - EAT 80/67°F COP HWC TC SC MBtu/h MBtu/h MBtu/h Operation not recommended 15.6 86.9 2.
RG SERIES ENGINEERING GUIDE RGS041 - Performance Data Single Speed Variable Speed ECM or 5-Speed ECM (1300 cfm) WPD EWT °F 20 30 40 50 60 70 80 90 100 110 120 HEATING - EAT 70°F COOLING - EAT 80/67°F Flow gpm psi ft. hd. 5.0 1.6 3.8 8.0 3.6 8.2 11.0 8.0 18.5 5.0 1.5 3.4 8.0 3.4 7.8 28.5 2.61 19.6 86.9 3.20 3.7 41.8 30.4 0.73 1.71 47.7 24.5 --- 11.0 7.9 18.1 29.5 2.66 20.4 87.5 3.26 3.8 42.4 31.0 0.73 1.61 47.9 26.4 --- 5.0 1.3 3.0 8.0 3.2 7.
RG SERIES ENGINEERING GUIDE RGS042 - Performance Data Single Speed Variable Speed ECM or 5-Speed ECM (1400 cfm) WPD EWT °F 20 30 40 50 60 70 80 90 100 110 120 HEATING - EAT 70°F COOLING - EAT 80/67°F Flow gpm psi ft. hd. 5.0 1.6 3.8 8.0 3.6 8.2 11.0 8.0 18.5 5.0 1.5 3.4 8.0 3.4 7.8 30.0 2.61 21.1 87.8 3.37 3.7 43.6 31.7 0.73 1.71 49.4 25.5 --- 11.0 7.9 18.1 31.0 2.66 21.9 88.5 3.42 3.8 44.2 32.3 0.73 1.61 49.7 27.5 --- 5.0 1.3 3.0 8.0 3.2 7.
RG SERIES ENGINEERING GUIDE RGS048 - Performance Data Single Speed Variable Speed ECM or 5-Speed ECM (1600 cfm) WPD EWT °F 20 30 40 50 60 70 80 90 100 110 120 HEATING - EAT 70°F COOLING - EAT 80/67°F Flow gpm psi ft. hd. 6.0 2.2 5.1 9.0 4.4 10.0 12.0 6.8 15.8 6.0 2.0 4.7 9.0 4.2 9.6 35.3 3.12 24.6 89.8 3.31 4.9 50.3 31.3 12.0 6.7 15.5 35.8 3.15 25.1 90.1 3.33 5.0 51.0 31.9 6.0 1.9 4.
RG SERIES ENGINEERING GUIDE RGS060 - Performance Data Single Speed Variable Speed ECM or 5-Speed ECM (2000 cfm) WPD HEATING - EAT 70°F COOLING - EAT 80/67°F EWT °F Flow gpm 9.0 3.8 8.7 20 12.0 6.3 14.5 15.0 9.7 22.5 9.0 3.6 8.4 12.0 6.1 14.1 43.8 3.89 30.5 88.3 3.30 5.9 72.0 49.1 0.68 2.86 15.0 9.6 22.2 46.5 4.01 32.8 89.5 3.39 6.1 73.0 50.0 0.68 2.68 30 40 50 60 70 80 90 100 110 120 psi ft. hd.
RG SERIES ENGINEERING GUIDE RGS070 - Performance Data Single Speed Variable Speed ECM or 5-Speed ECM (2200 cfm) WPD HEATING - EAT 70°F COOLING - EAT 80/67°F EWT °F Flow gpm 12.0 4.3 9.8 20 15.0 5.6 13.0 18.0 9.0 20.8 12.0 4.1 9.4 15.0 5.9 13.6 52.0 4.82 35.5 89.9 3.16 7.0 73.0 46.1 0.63 3.18 18.0 8.8 20.3 53.7 4.96 36.8 90.6 3.17 7.3 74.0 47.0 0.64 2.99 12.0 3.8 8.8 15.0 5.2 12.0 58.4 5.00 41.3 92.6 3.42 7.8 74.6 49.3 0.66 3.38 18.0 8.6 19.8 60.
RG SERIES ENGINEERING GUIDE Wiring Schematics Aurora Base Control 208-230/60/1 PSC with GeoStart Compressor S PSC Blower Motor C Black R Blue Cap Grn Red Run Winding Pink Active Soft Start Blue Red Brn Wht Tan Pink Blue Start Winding Black Common Winding Unit Power Supply 208-230/60/1 G Cap P3 3 Airflow Settings H M T2 T1 CC L2 L Note 1 L1 Green (93) Black White Black 1 RB 3 Black Black (95) L1 L1 Red (97) L2 L2 L3 L3 Red 208V Note 2 Blue 230V Ground Neutral D
RG SERIES ENGINEERING GUIDE Wiring Schematics cont.
2 Polarized connector 11/13/09 Occupied Switch Power blocks Pump Relay Blower Relay Rectified Solenoid Compressor Plug Reversing Valve coil Terminal Board Freeze Detection Phase Guard Module Blue (10) PB2 2 1 3 Note 1 OS ES Blue (32) LP Note 14 DF/FP CP 31 32 Gray (65) Yellow (51 ) Yellow/White (52) 38 DI8 DI7 47 48 Blue (72) Yellow (21 ) Orange (30) Pink (25) Black/White (29) DI5 52 DI1 9VDC 55 56 DI2 54 DI3 DI4 DI6 51 Gray (26) Blue (27) 53 50 Red (24) Violet (23) DI 3
Compressor Solenoid 3 2 3/19/12 1 OS PB1, PB2 PRRBRCP RV TB FD PGM RH - Occupied Switch Power blocks Pump Relay Blower Relay Rectified Solenoid Compressor Plug Reversing Valve coil Terminal Board Freeze Detection Sensor Phase Guard Module Reheat Valve Coil Blue (10) Black (76) 1 2 3 PB2 Note 1 OS ES Blue (32) LP DF/BP DI11 45 Green (70) 51 52 Gray (26) 55 56 54 Black/White (29) Orange (30) Pink (25) 53 Red (24) Blue (27) 50 Violet (23) 49 48 Yellow (21) Black (22) DI8 B
3/8/12 2 97P822-04 3 OS PB1, PB2 PRRBRCP RV TB FD PGM RH - 1 Compressor Contactor Condensate Overflow Sensor Compressor Proving Compressor Solenoid Discharge Air Temperature Sensor Dirty Filter or Blower Proving Dehumidification Switch or Humidistat Emergency Shutdown High Pressure Switch Low Pressure Switch Compressor Solenoid Rectified Compressor Solenoid Plug Occupied Switch Power blocks Pump Relay Blower Relay Rectified Solenoid Compressor Plug Reversing Valve coil Terminal Board Freeze Det
RG SERIES ENGINEERING GUIDE Wiring Schematics cont.
RG SERIES ENGINEERING GUIDE Engineering Guide Specifications Option: A Super Quiet Sound package shall include multi-density full coverage compressor blanket. General Furnish and install water source heat pumps as indicated on the plans. Equipment shall be completely assembled, piped and internally wired. Capacities and characteristics as listed in the schedule and the specifications that follow.
RG SERIES ENGINEERING GUIDE Engineering Guide Specifications cont. Option: ThermaShield coated water-to-refrigerant heat exchanger, water lines and refrigerant suction lines shall be insulated to prevent condensation at low liquid temperatures below 50°F. Space humidity high and low alarm limits (building automation system only) - The control has a high and low alarm limit that can be enumerated over a building automation system.
RG SERIES ENGINEERING GUIDE Engineering Guide Specifications cont. A detachable terminal block with screw terminals will be provided for field control wiring. All units shall have knockouts for entrance of low and line voltage wiring. The blower motor and control box shall be harness plug wired for easy removal. Swivel connection provides union between heat pump and piping system. The hoses feature brass fittings, stainless steel ferrules.
RG SERIES ENGINEERING GUIDE Revision Guide Pages: Date: By: Updated with Aluminum Air Coils 29 Oct 2013 DS 35-36 Updated 009-012 Horizontal Dimensions 29 Oct 2013 DS 39-41 Updated Compressor LRA with GeoStart 31 Jul 2013 DS All Updated Nomenclature to Reflect New Variable Speed ECM Motor 13 Feb 2013 DS All Updated to Aurora 2.
Product: Type: Size: RG Series Geothermal/Water Source Heat Pump 0.75-6 Ton Document Type: Form: Supercedes: Engineering Guide 146.00-EG1A (1013) 146.