Instructions / Assembly

Troubleshooting
Symptom Cause Solution
Machine Won't
Run
Power outage Restoration of power supply
Power plug is not connected
well
Connect the plug to the socket
Room temperature over 113
or below 38
The machine's protection device is
activated so that the machine d oes not
run
Low Air Flow
Filter with dirt accumulation
Cleaning filters
The air inlet or outlet is blocked Remove obstructions
Refrigerant leakage Contact agent or manufacturer for repair
Water Leakage Clogged outlet pipe
Remove the panel to remove the
blockage at the water pipe, or water
outlet
Loud Noise
Machine Is Not level
Move the dehumidifier to flat, firm
ground
Filter Mesh is Blocked
Clean the filter mesh according
toinstructions listed in manua l
Trouble Code:E1
Temperature and humidity
sensor failure
Check, or replace the temperature and
humidity sensor
Trouble Code:E2 Coil sensor failure Check, or replace the co il sensor
Trouble Code:CL
and the compressor will stop immediately, and the fan delay will be
executed according to th e set value (F1 default 0, delay 5 seconds to stop).
When the ambient temperature rises t o 39, normal operation will
resume.
Trouble Code:CH
When the ambient temperature Tr> 113, "CH" will be
displayed, the compressor will stop immediately, and t he fan delay will be
executed according to th e set value (F1 default 0, delay 5 seconds to stop);
when the ring temperatu re 108, normal operation will be resumed.
Trouble Code:L0
When the ambient hu midity Hr< 20%, "LO" will be displayed, the
compressor will stop immediately, and the fan delay will be executed
according to the set value (F1 default 0, delay 5 seconds to stop). After the
humidity rises > 20%, resume normal work.
Trouble Code:HI
When the ambient humidity Hr>95%, "HI" is displayed and the
compressor and fan work normally.
After the humidity falls back to <95%, it will resume normal operation.
22