Specifications
40 RK0YG302 © Danfoss 05/2007
EKC 100
EKC 100
Temperature control
Introduction
The controller is used for temperature control of refrigeration
plant.
Operation, setting and programming are optimised and simplied
as much as possible.
The controller is designed so that temperature control and
defrost control can be made via pump down or start/stop of the
compressor.
Parameter
Min.
value
Max.
value
Factory
setting
Function Code
Normal operation
Temperature (set point) --- -60°C 50°C 0°C
Thermostat
Dierential r1 1 K 20 K 2 K
Display adjust r4 -20 K 20 K 0 K
Compressor
Min. ON-time c1 0 min. 30 min. 0 min.
Min. OFF-time c2 0 min. 30 min. 0 min.
Defrost
Defrost stop temperature d2 0°C 25°C/o 25°C/o
Interval between defrost
starts
d3 0 hours 48 hours 8 hours
Max. defrost duration d4 0 min. 99 min. 45 min.
Displacement of time on
cutin of defrost at start-up
d5 0 min. 15 min. 0 min.
Miscellaneous
Delay of output sigal after
start-up
o1 0 min. 15 min. 0 min.
Fault code
Sensor error Er
SW = 1.1X
Menu survey
Regulation starts when the voltage is on.