Specifications
RK0YG302 © Danfoss 04/2007 187
Furhter information!
Manual: RS.8D.M/DKRCE.EC.000.M2.22
Important
Installation of data communication cables and repeaters must-
comply with the requirements mentioned in the document:
Data communication between ADAP-KOOL® Refrigeration con-
trols. Literature number = RC8AC.
AK input-output module family
Put line-ups of up to nine self-addressing I/O modules wherever
you need them, and in any combination. Modules are available
with:
• 8 relays (with or without override)
• 8 relays (with or without override) and 8 universal inputs
• 8 universal inputs
• 8 digital inputs (high and low voltage versions)
• 4 bi-polar EEPR outputs
Each module lineup begins with a communications and power
module that is connected to the AK-SC 255 system controller via
Echelon® Lonworks®. No wiring to individual modules is required
because of a unique intermodular bus.
AK-SC 255 Solution components:
• Communication module
• I/O modules
• Pulse counter
Type Function Code no.
AK-SC 255 Refrigeration 080Z2047
AK-SC 255 Refrigeration, light, HVAC 080Z2048
AK-SC 255
Refrigeration, light, HVAC
For DIN rail mounting (without screen)
080Z2083
Ordering
Recommened individual controller capacity(s)
- per AK-SC 255
Type AK-CC 750 60 Max. congured evaporator section 150
Type EKC (SNMP, Lonworks) 120 1 controller per evaporator section
Recommened Remote AK I/O capacity (in addition
to controllers)
AK I/O
64 points
(max 8 AK CM)
Analog (General I/O, HVAC, Lighting)
AK I/O
64 points
(max 8 AK CM)
Digital (General I/O, HVAC, Lighting)
Available Network Protocol
Ethernet Port (used for EKC SNMP controllers, 255 host network & remote AKA65 software tool)
RS 485 Host Bus (used for multiple AK-SC 255)
MODBUS
RS232 Port (used for AKA 65 software tool)
Modem Port (used for serial modem)
LonWorks TP78 (used for AK/IO modules)
LonWorks RS 485 (use TP78 - RS 485 bridge - 084B2254)
Power KWh Meter Pulse input capacity AK-XM107A Pulse Module, Max 8 inputs
Additional AK-SC255 units interconnected (Host
Network)
Max of 10 AK-SC255 units (1 Master & 9 Slave)
History Data points 600
History Capacity 10 minute samples on 120 points = 1 year
Remote connection software
AKA 65 v5.1 : Modem
Ethernet
Serial
Recommended Modem Support
Zoom V.92 56k Modem (Model 3049)
AKA 231 ‘Phoenix’ modem
Environmental Data
Operating temperature
32 to 104°F (0 to +40°c) @ 95% RH (non condensing)
32 to 122°F (0 to +50°c) @ 0 to 90% RH (non condensing)
Storage temperature -4 to 122°F (-20 to +50°c)
Technical data
AK-SC 255