Data Sheet
5-3 Altitude
From sea level to 5,000 Meter (operation ) and 5,000 Meter (non operation )
6-0. Safety
6-1. Hi-Pot Test
L、N--> FG:1800Vac, 10mA, 2S
P --> S:3000Vac, 10mA, 2S
6-2. Insulation Test
500Vdc, 2Sec. between primary and secondary circuit
IR should ≧ 100 MΩ .
6-3. Leakage Current
≦250uA at 240Vac/50 Hz
6-4. Safety
UL, CUL, TUV, CB, CE, FCC, BSMI, RCM, PSE, CCC
6-5. EMS
Items Specification Reference
Contact: ±4KV
ESD
Air: ±8KV
IEC 61000-4-2
RS
Frequency: 80~1000MHz
Field Strength: 3V/M, 80% AM(1KHz)
IEC 61000-4-3
EFT
1.0 KV on input AC power ports.
IEC 61000-4-4
Line to Line: ± 1KV (peak)
SURGE
Line to F.G : ± 2KV (peak)
IEC 61000-4-5
6-6. EMI
Comply with Standards
CISPR 32, EN 55032 Class B
FCC PART 15 Class B
7-0. Mechanical Characteristics
7-1. Physical Size : 160mm (L) * 64 mm (W) * 30 mm (H)
7-2. Enclosure material : 94V-0 minimum