Data Sheet

2-7. Inrush Current
60A at 110 Vac
120A at 220 Vac At cold start, maximum load.
2-8. Line Regulation
This line regulation is less than ± 1%, of rated output voltage @ full load .
2-9. Hold Up Time
8.3 mSec., @ Normal line, with full load.
2-10. Rise Time
50 mSec., @ 115V AC input, with full load.
From 10% to 90% of output voltage.
2-11. Turn-ON Time
The output voltage should rise to 90% of rated output voltage
in less than 3 SEC. from AC apply to 110Vac start up.
3-0. Output Requirements
3-1. Output Voltage and Current
3-2. Load Regulation
3-3. Dynamic Load Regulation
±5% excursion for 50% - 100% or 100% - 50% load change of DC output at
any frequency up to 1KHz(duty 50%)
3-4. Ripple Noise
The power supply shall not exceed the following limits on the indicated voltage for 60Hz
or 50Hz ripple, Switching frequency ripple and noise and dynamic load variations
measured with a 20MHz bandwidth
Output Voltage
(Vdc)
Current
Min.(A)
Current Max.(A)
+12V 0 5.0A
Voltage (Vdc) Tolerance (%) Regulation (Vdc)
+12V +5/, -5 11.4~12.6V