Technical information
INPUT
3. OPERATION
• Keypad selection of input type (refer to Cycle 3).
Operator Interface
• Display resolution: 0
.
1ºF/C or 1ºF/C (RTD-Pt100).
• Input sample rate: 10 per second (10Hz).
• Accuracy: Thermocouples J, K, T, N, E: 0.2% of span, ±1ºC, ±1 digit.
Thermocouples S, R: 0.25% of span, ±3ºC, ±1 digit.
Pt100: 0
.
2% of span, ±0.5ºC, ±1 digit.
• Input impedance: Thermocouple: >10MΩ
• Pt100 measurement: DIN 43760 standard (α=0
.
00385).
3-wire circuit, cable resistance compensation.
Excitation current: 170µA.
PID CONTROL:
• User-selectable as: ON-OFF w/ adjustable hysteresis, or manual P, PI, PID and
PID-Autotune.
• Proportional Band (Pb): 0 = ON/OFF control; or 1% to 500% of maximum input
span.
• Integral (Ir): 0 = off; or 0.01 to 25.00 rep/minutes
• Derivative (Dt): 0 = off; or 1 to 250 seconds.
(Figure 2)
• Cycle-Time: 0.5 to 99.9 seconds (for PWM-PID output control).
• PID-Autotune: start from the front panel.
Process Display - PV
: shows the PV (
P
rocess
V
ariable) value, and used when
configuring the parameters of the controller.
OUTPUT: model TC33-1100-AC:
Setpoint
Display
– SV
: shows the SV (
S
etpoint
V
ariable) value, and used when
• One isolated Pulsed DC Output Control (12Vdc pulsed @ 15mA max.).
configuring the parameters of the controller.
• One SPST Relay Alarm (without contact suppression):
Resistive: 3A @ 250VAC / 3A @ 125VAC / 3A @ 30VDC
Control – C
LED: indicates that the controller is active, with control. If there is
Inductive: 2A @ 250VAC / 2A @ 30VDC
a control output programmed as PWM or ON/OFF, the output
Dielectric Strenght: 750Vrms between open contacts (at sea level for 1 min.)
LED will reflect the actual state of the output (ON or OFF).
If there is a Linear 4-20mA control output, the LED will be
OUTPUT: model TC33-2010-AC:
continuos ON.
• One isolated Linear Control sourcing 4-20mA output @ 500 ohms max. load.
Auto-Tune – AT
LED: indicates that the controller is in Auto-Tune mode,
• Two SPST Relay Alarms (without contact suppression):
(LED On = Auto-Tune active).
Resistive: 3A @ 250VAC / 3A @ 125VAC / 3A @ 30VDC
Alarm 1 – AL1
LED: indicates the status of the alarm, (LED On = alarm active).
Inductive: 2A @ 250VAC / 2A @ 30VDC
Dielectric Strenght: 750Vrms between open contacts (at sea level for 1 min.)
Alarm 2 – AL2
LED: indicates the status of the alarm, (LED On = alarm active).
2.1 MAIN DIMENSIONS, AND PANEL CUTOUT:
SET UP
key: used to set up menu cycles.
6 mm
100 mm
Panel Cutout
45.2 mm to 45.8 mm
4
5
.
2
m
m
t
o
4
5
.
8
m
m
A2
A1
SET
UP
AT
AutomationDirect
Decrease
key: used to change parameter values.
Increase
key: used to change parameter values.
When the controller is initially energized, the firmware version is displayed
for approximately 4 seconds, after which the controller starts normal
operation. The values of PV (temperature), and SV (setpoint) are displayed
and the outputs are enabled after 6 seconds.
(Not to scale)
(Figure 1)
4 5