Operating instructions
21
Heating
Model CFM GPM dP Capacity (1000 BTU/hr)
(Ft. of Head) 120
o
F EWT 140
o
F EWT
3.0 12.0 12.2 17.4
3 HBC-3
310 2.0 6.0 11.7 16.7
1.0 1.9 10.5 14.9
3.5 18.0 16.1 22.9
4 HBC-3
510 2.5 10.0 15.7 22.3
1.5 4.5 14.5 20.6
4.0 10.0 19.7 28.0
5 HBC-3
600 3.0 5.9 19.1 27.1
2.0 2.9 17.9 25.4
5.5 17.0 24.1 34.3
6 HBC-3
730 4.0 10.0 23.4 33.3
2.5 4.2 21.9 31.2
6.0 11.0 29.2 41.5
8 HBC-3
870 4.5 6.5 28.3 40.2
3.0 3.0 26.3 37.4
8.0 14.0 34.9 49.7
10 HBC-3
1070 6.0 8.1 34.2 48.6
4.0 3.9 32.0 45.6
10.0 22.0 45.9 65.3
13 HBC-3
1400 7.5 13.0 44.8 63.7
5.0 6.2 41.9 59.5
Ratings at 70
o
F entering air temperature
Cooling
Capacity (1000 BTU/hr) at 45
o
F EWT
Model CFM GPM dP 80
o
F DB/67
o
F WB 75
o
F DB/63
o
F WB
(Ft. of Head) TH SH TR TH SH TR
2.8 10.3 10.8 6.9 8.0 8.6 6.3 6.4
3 HBC-3
310 2.1 8.0 10.1 6.7 10.0 8.1 6.1 8.0
1.6 4.2 9.2 6.4 12.0 7.5 6.0 10.0
3.6 19.0 14.2 9.3 8.0 11.6 8.4 6.7
4 HBC-3
510 2.8 12.5 13.4 9.0 10.0 11.0 8.1 8.1
2.1 7.6 12.3 8.4 12.0 10.0 7.6 10.0
4.5 12.0 17.4 11.5 8.0 14.0 10.2 6.4
5 HBC-3
600 3.3 8.0 16.3 11.0 10.0 12.9 9.7 8.0
2.6 4.5 15.1 10.5 12.0 12.0 9.2 9.5
5.7 18.0 22.2 15.5 8.0 17.8 14.1 6.5
6 HBC-3
730 4.3 10.5 20.7 14.4 10.0 16.7 13.6 8.0
3.3 6.9 19.4 14.4 12.0 15.6 13.1 9.8
6.4 12.1 25.2 18.3 8.0 20.6 16.5 6.6
8 HBC-3
870 4.7 8.0 23.2 17.4 10.0 19.0 15.9 8.3
3.7 4.5 21.4 16.6 12.0 17.9 15.5 10.0
8.4 15.0 32.2 22.3 8.0 25.8 19.7 6.5
10 HBC-3
1070 6.0 8.0 28.0 21.0 10.0 23.4 18.6 8.3
4.6 5.0 26.4 20.2 12.0 21.6 17.8 10.0
10.8 25.0 42.0 29.6 8.0 34.6 27.2 6.7
13 HBC-3
1400 7.8 14.0 37.0 28.0 10.0 30.8 25.8 8.0
6.0 8.7 34.5 27.2 12.0 28.2 24.8 10.0
TH = Total Heating Capacity SH = Sensible Heating Capacity TR = Water Temperature Rise
Table 5 – Fan Coil Data
INDICATOR LIGHTS
CONDITION PWR ASC LP HP FP COMMENTS
AC power applied Blown fuse or power removed.
" X X ASC indicator on for 4' 35" on power initialization.
" X Power applied - unit running or waiting for a call to run.
Run cycle complete X X ASC indicator ON for 30 to 60 seconds after compressor shutdown.
LP (HYD heating - before call) X X Indicates LP switch position (ON = open).
LP (HYD heating - after call) X X X Lockout, indicators latched and resettable by removing power.
LP (HYD cooling - before call) X X Indicates LP switch position (ON = open).
LP (HYD cooling - after call) X X X Lockout, indicators latched and resettable by removing power.
HP (HYD heating - before call) X X Indicates HP switch position (ON = open).
HP (HYD heating - after call) X X X Lockout, indicators latched and resettable by removing power.
HP (HYD cooling - before call) X X Indicates HP switch position (ON = open).
HP (HYD cooling - after call) X X X Lockout, indicators latched and resettable by removing power.
FP (F/A heating - before call) X X Indicates FP switch position (ON = open).
FP (F/A heating - after call) X X X Lockout, indicators latched and resettable by removing power.
FP (F/A cooling) X FP switch disabled in cooling mode.
Table 6 – Controller #20-1038 LED Indicator Chart