Instructions

Operation and parameterization 64
Manual econ sens3 Version 3.0
In the Events submenu up to 6 parameters are recorded for each event. The description is found in the
following table (unused parameter=0):
Event
Parameter 1
Parameter 2
Parameter 3
Parameter 4
Parameter 5
Parameter 6
Frequency fluctuations
Measured
frequency [mHz]
Ratio to
measured
nominal
frequency
[%]
0
0
0
0
Slow voltage changes
Measured
voltage L 1
[dVrms]
Measured
voltage L 2
[dVrms]
Measured
voltage L 3
[dVrms]
Ratio of
maximum
measured
voltage to
nominal voltage
[%]
0
0
Fast voltage changes
Voltage change
L 1 [dVrms]
Voltage change
L 2 [dVrms]
Voltage change
L 3 [dVrms]
0
0
0
Flicker sharpness level
Short term
flicker L 1
[-/10]
Short term
flicker L2 [-
/10]
Short term
flicker L 3
[-/10]
0
0
0
Voltage dip
Lowest ratio to
measured
nominal voltage
for L1 [%]
Lowest ratio to
measured
nominal voltage
for L2 [%]
Lowest ratio to
measured
nominal voltage
for L3 [%]
Duration [ms]
0
0
Voltage interruption
Lowest voltage
L1 [dVrms]
Lowest voltage
L2 [dVrms
Lowest voltage
L3 [dVrms]
Duration [ms]
0
0
Temporary transient
overvoltage
Highest ratio to
measured
nominal voltage
L1 [%]
Highest ratio to
measured
nominal voltage
L2 [%]
Highest ratio to
measured
nominal voltage
L3 [%]
Duration [ms]
0
0
Transient overvoltages
Overvoltage L1
[dVrms*s]
Overvoltage L2
[dVrms*s]
Overvoltage L3
[dVrms*s]
Duration [ms]
0
0
Voltage asymmetry
Maximum
asymmetry L1
[%]
Maximum
asymmetry L2
[%]
Maximum
asymmetry L3
[%]
Duration [ms]
0
0
Harmonic voltage
Maximum
harmonic
distortion L1
[%]
Maximum
harmonic
distortion L2
[%]
Maximum
harmonic
distortion L3
[%]
Duration [ms]
0
0
Current limit
Overcurrent L1
[dArms*s]
Overcurrent L2
[dArms*s]
Overcurrent L3
[dArms*s]
Duration [ms]
0
0
Frequency shift
Frequency
before change
[mHz]
Frequency
before change
[mHz]
0
0
0
Vector jump
Vector jump L1
[°]
Vector jump L2
[°]
Vector jump L3
[°]
0
0
Neutral conductor voltage
Highest neutral
conductor
voltage [dVrms]
Duration [ms]
0
0
0
0
Supply voltage on/off
1=on, 0=off
0
0
0
0
0
Harmonic current
Maximum
harmonic
distortion L1
[%]
Maximum
harmonic
distortion L2
[%]
Maximum
harmonic
distortion L3
[%]
Duration [ms]
0
0
Change to internal clock
time
Time difference
[s]
0
0
0
0
0
Low consumption trigger
Energy
consumption
limit [kWh]
Duration of
low energy
consumption
[min]