Operation and parameterization 58
Manual econ sens3 Version 3.0
The input is scanned in 5 ms intervals. The collected scans are debounced and only if 3 consecutive
scans are stable will the recognized level be changed. The following image shows the debouncing
process. Peaks for the time from one or two scans are filtered out.
Time
Vin [V]
2.5V
1.5V
In
Out
5ms