User manual
Managing DE Devices using MC Toolkit Software
5.5. Online configuration
82 MC Toolkit User Manual Revision 12
May 2013
DE Main Menu Procedures
General (ST 3000 / ST 800)
(STT 3000)
PV Type (r/w)
Select: Dual Range (STDC) or
Single Range or Single Range
w/SV
Communication Mode
(r/w) Select: Analog or DE 4
Byte or DE 6 Byte
FS Direction (r)
(Upscale or Downscale;
selection is jumpered in the
transmitter).
Line Filter (r)
Select: 50hz or 60hz.
T/C Fault Detect (r/w):
Select: Enabled or Disabled.
DE
Configure
ST 3000 / ST 800
STT 3000
LRL (r): Lower Range Limit
URL (r): Upper Range Limit
LRV (r/w): Lower Range Value
URV (r/w): Upper Range Value
PV Units (r/w)
Selection of scaling value (default: inches of H
2
O@39°F)
SV Units (r/w)
Selection of scaling value (°C/°F)
Sensor Type (r)
Sensor Type associated with the transmitter
Damping (r/w)
Selection of level of digital noise reduction
Span (r)
Process Range (URL - LRL)
Conformity (r/w) (ST 3000 / ST 800)
Selection of conformity to input form: Linear or Square Root
Linearization (r/w) (STT 3000)
Selection of conformity to input form: Linear or Non Linear