User manual
3. Getting Started
3.7. DE/ HART Modem Firmware
Revision 12 MC Toolkit User Manual 23
May 2013
Select Modem Diagnostics under the Modem Menu. Modem Diagnostic screen will be displayed
Figure 3-5 Modem Menu
Figure 3-6 Modem Diagnostics screen
Check and verify that the Modem Firmware version field displays 2.0. If it is less than 2.0, upgrade the
modem firmware using the Instructions guide 34-ST-25-33 that is shipped with the MC Toolkit product.
Make sure you complete the Modem firmware upgrade before Connecting MCT 101 or MCT 202 to the
devices