6.3. MC Toolkit application software troubleshooting scenarios
132 MC Toolkit User Manual Revision 12
May 2013
MESSAGE
Description Resolution / CORRECTIVE
ACTION
The transmitter is in Output Mode.
Are you sure you want to
terminate the connection?
User tried to Exit MC Toolkit application
while the DE Transmitter is still in Output
Mode.
Same as Description
The changes you have made are
about to be sent to the transmitter.
Continue?
Values entered into this display will be
written into transmitter memory.
Informational message
Please make sure you are
connected to a DE device.
Sending DE commands to a non-
DE device could potentially cause
a process upset.
DE communications (~ 4-20 mA
amplitude) could cause erroneous
transmission in non-DE protocols.
Same as Description
Leaving the Main Menu will require
an upload in order to return. Are
you sure you want to do this?
A new Upload will require approximately
60-second wait.
Same as Description
Put loop in Manual ... Trips
secured?
Changing values of transmitter
parameters can cause process upset.
Same as Description
Conformity must be square root to
select this unit.
Units for Flow indications are available
only when Square Root conformity is
selected.
Same as Description
Are you sure you want to Reset All
Corrects to factory defaults?
Executing Reset All Corrects will overwrite
all user input calibration values (Zero,
LRV, URV) with factory-default values.
Same as Description
Are you sure you want to place the
transmitter in output mode (?)
In Output Mode, output current will be set
to the selected constant value, rather than
to calculated
Same as Description
Square Root is not allowed for GP
and AP Sensor Types.
Square Root conformity is available only
for FLOW (DP) input applications.
Same as Description