User Manual
Fusing and Setting
Testing and Troubleshooting
-14-
-Fusing position
The combiner box has built-in fuses for each string, so there is no need
to add extra fuse in between the solar panels and combiner box, neither
from the combiner box to inverter.
Even though the hybrid inverter has built-in fuse, it’s better to add one
fuse in between it and the battery bank. For a 24V 3500W inverter, the
current it can take from the battery bank should be about 146A, so a
180A fuse is recommended.
Testing
Test all electrical and electronic components of your system before
commissioning it. Follow the instructions in the guides supplied with the
components and equipment.
·Test modules connected in series before they are connected to the
system.
·To determine Voc and Isc in the following tests, the module(s) must be
exposed to the sun and not connected to a load. Observe personal
safety when making these measurements.
Fuse