Installation guide

8
Eclipse RatioMatic Burners, RM Series, V5, Installation Guide 110, 11/11/2011
Figure 3.2. Mounting Pattern
Chamber Wall
Make sure the chamber wall is strong enough to
support the weight of the burner . If necessary, reinforce
the mounting area.
If the chamber insulation extends beyond the nozzle
position of the burner, taper the insulation around the
combustor at a minimum 45° angle. Refer to Datasheets
to determine the position of the nozzle relative to the
chamber wall.
Figure 3.3. Chamber Wall
Burner Mounting
Mount burner to chamber wall using four (4 or 8) customer
supplied nuts and lock washers, as required.
Both Alloy and Silicon Carbide (SiC) Combustor
1. Be sure gasket is installed between burner and
chamber wall .
2. Pack fiber insulation around the combustor to a depth
not beyond the nozzle position, as illustrated.
Figure 3.4. Alloy Combustor
Placing insulation around the combustor beyond
the burner nozzle position will decrease
combustor life.
3. No gasket is supplied or required between the burner
and combustor.
Silicon Carbide (SiC) Combustor Only
SiC combustor is fragile. Handle with care.
If the SiC combustor is not already attached to the burner,
be sure gasket is installed between the SiC combustor
and flange . Tighten the screws which hold the flange
to the burner evenly. Do not over tighten.
Figure 3.5. Silicon Carbide (SiC) Combustor
When replacing SiC combustor be sure gasket
is installed, tighten screws evenly, and do not use
excessive force.
Refractory Block
1. Ensure gasket is installed between burner and
block holder .
2. Ensure gasket is installed between block holder
and chamber wall .
3. Support the weight of refractory block with hard brick
work anchored to the furnace shell . Fill the 1/2"
space between block and the three unsupported
sides with soft gasket material .
“C”
RM0050 - RM0700
“C”
RM1000 - RM3000
NOZZLE
POSITION
4
2
45° Minimum
Chamber
Insulation
Fiber insulation
Chamber
insulation
1
4
2
NOZZLE
POSITION
CAUTION
CAUTION
POSITION
1
3
5
6
4
2
Fiber insulation
Chamber
insulation
CAUTION