Installation guide
Eclipse RatioMatic v3.10 - Installation Guide No. 110, 7/1/03
23
Bypass start gas with fuel orifice meter:
Main gas
shut-off
valve train
NC
NC
1. Drive control motor to low fire.
2. Be sure combustion air blower is running.
3. Be sure main gas manual shut off valves are closed.
4. Prepare to measure bypass gas flow at the fuel orifice
meter
4.
5. Open manual shut off valve 1 in the bypass.
6. Set the system to operate on bypass gas only.
7. Attempt to ignite burner by energizing spark and bypass
gas solenoid valves
2.
8. If burner does not ignite:
a. Attempt to ignite burner again to purge air from the
gas piping.
b. If burner still does not ignite, turn ALO adjusting screw
3 a half turn counterclockwise to increase gas flow.
c. Attempt to ignite burner.
d. Repeat steps b and c until burner ignites. If necessary,
refer to Chapter 5 for troubleshooting tips.
9.
Adjust bypass gas flow with ALO adjusting screw 3 to
achieve the low fire gas flow indicated on data sheet.
Refer to the fuel orifice meter literature for instructions
on flow measurement.
Note:
When firing into negative or fluctuating chamber pressures,
a higher bypass gas flow may be necessary.
Note:
If viewing the flame, it should be blue with flashes of yellow.
The flame should be completely within the combustion tube.
When firing propane or butane, a proper low fire flame may
have sustained flashes of yellow.
10. Verify the bypass gas flame:
a. Shut off gas. When chamber temperature is below
250°F (121°C), shut off combustion air blower.
b. Restart combustion air blower and ignite burner.
c. Verify repeatability of ignition and low fire flame signal.
Step3: Ignite the burner
Procedure D:
Bypass start gas with fuel orifice
meter
Adjustable Limiting Orifice
(ALO)
1
2
3
4