Installation guide

Eclipse RatioMatic v3.10 - Installation Guide No. 110, 7/1/03
16
INTRODUCTION
In this chapter, you will find instructions on how to adjust,
start, and stop the burner system. Become familiar with
burner control methods before attempting to make
adjustments..
Danger:
The RatioMatic burners, described herein, are
designed to mix fuel with air and burn the
resulting mixture. All fuel burning devices are
capable of producing fires and explosions if
improperly applied, installed, adjusted,
controlled, or maintained.
Do not bypass any safety feature; fire or
explosion could result.
Never try to light a burner if it shows signs of
damage or malfunction.
Adjustment steps:
1. Reset the system
2. Set low fire air
3. Ignite the burner
4. Set low fire gas
5. Verify settings
Reset procedure:
1. Set the low gas pressure switch to 20% below the “Main
gas inlet pressure” range as specified in the appropriate
data sheet.
2. Set the high gas pressure switch to 20% above the “Main
gas inlet pressure” range as specified in the appropriate
data sheet.
3. Close all the burner gas valves, manual and automatic.
4. Try to ignite the burner; be sure the flame monitoring
system indicates a flame failure.
ADJUSTMENT
Adjustment, Start &
Stop
44
44
4
Step 1: Reset the system