Service manual
Pre-operational System Testing
67
DCB, DCFCB and DCFCTB Models
Pre-operational System Testing
The output sound level of a siren is capable of causing severe hearing discomfort or
permanent hearing damage. Therefore, ALWAYS wear adequate hearing protection
and minimize exposure time when performing any testing or maintenance on the
siren.
Failure to properly test the siren system before placing into service may prevent the
siren from operating in an emergency. The following tests and calibrations must be
performed by an experienced technician prior to using the siren system.
Initial Sensor Adjustments and Testing
To ensure proper and reliable two-way status operation, the operation and alignment
of the sensors must be confirmed when the siren and control are installed. All of the
sensors are factory adjusted and the following alignment instructions may only
pertain to tuning replacement sensors.
Rotation Current Sensor
Locate the rotation current board (2005221) on the backplane of the control cabinet
with the blue current sensor (refer to Figure 10 DCFCTB Wiring Diagram on page
54). This board is preset at the factory and should not be adjusted.
To check the board for proper operation, do the following:
1. Verify that the output at JP2-2 is high (4 – 5VDC).
2. Activate a siren function by momentarily depressing one of the function
pushbuttons on the controller board.
3. Measure the DC voltage on TP2. The voltage should correspond to the DC
current draw of the siren motor (0.8 ADC, +/- .3 A).
4. Verify the output JP2-2 is low (0-1 VDC) for the duration of the siren function.
Chopper Current Sensor
Locate the chopper current board (2001062) on the backplane of the control cabinet
(refer to Figure 10 DCFCTB Wiring Diagram on page 54).
Adjustment Procedure
1. Using Pot 1, adjust the voltage at TP2 to 7 VDC.
2. Using Pot 2, adjust the voltage at TP4 to 4.5 VDC.










