Specifications
LONWORKS® LN-Series Network Communication and Interface Guide Technical Bulletin 27
c. Reapply power to the i.LON 10 Ethernet Adapter while continuing to hold
the service pin until the wink and connect Light-Emitting Diodes (LEDs)
illuminate (10 seconds).
Note: When the LEDs illuminate, it means that the security access reset has
been performed properly.
3. To communicate with the i.LON 10 Ethernet Adapter, verify that your
computer is on the same subnet as the i.LON 10 adapter, which is 192.168.1.x.
If the computer’s subnet is different, open a DOS command prompt and type in
the following command: route add 192.168.1.0 mask 255.255.255.0
%computername%
4. Open your Internet browser and enter the following address:
http://192.168.1.222/config/
5. Select the General tab from the menu bar of the i.LON 10 Ethernet Adapter
properties screen (Figure 19).
6. Set the user name and password when prompted.
7. Set the Transmission Control Protocol (TCP)/IP parameters.
8. We recommend that you disable the following security options:
• Allow HTTP Access
• Allow TFTP Access
• Allow Access to Secure Pages Without Security Access Reset
Figure 19: i.LON 10 Properties Screen — General Tab