User`s guide
PCC-10 User's Guide 3-3
PCC-10 Initialization
In most cases, PCC-10 card initialization occurs automatically upon insertion.
Manual initialization will be required following software installation to a directory
other than C:\LONWORKS, or moving of the PCC-10 system images.
To manually initialize the PCC-10 card, verify that the control panel’s System
Image Path entry is correct, then click the Apply button.
An error will be reported if an attempt is made to modify the transceiver type
before the PCC-10 card is initialized. Testing the card with the Diagnostics button,
as suggested by the error message, produces the diagnosis: “Image file not found.”
In this case, return to the control panel’s main dialog box, and manually initialize
the PCC-10 card.
Device Specific Settings
The PCC-10 specific options consist of five separate controls (figure 3.2). These
controls are defined as follows:
Figure 3.2 PCC-10 Specific Controls
Device Selected
This setting controls which PCC-10 card is selected for configuration. The
PCCLON1 and PCCLON2 drivers are installed by the installation software. If
additional drivers have been manually installed, one or both of PCCLON3 and
PCCLON4 will also be available.
Automatic Flush Cancel
This setting controls whether the device driver will automatically force the network
interface (for the selected PCC-10 card) to leave the post-reset flush state whenever
it is reset. The post-reset flush state prevents any inbound or outbound network
traffic following a reset. If this box is not checked, it is up to the client application
to manage this state. If it is checked, the device driver will automatically allow
network traffic to resume. The default is checked.