Owner manual
OpenLNS Programmer's Reference 975
lcaErrNsUnsupportedInfo 28
The requested information is not available from an application node. For example,
transceiver status, SI/SD data, and network variable names are not always stored in the
node.
lcaErrNsOutOfRange 29
The value assigned to a property or parameter is either out of range, or invalid.
lcaErrNsEventFailure 30
The generation of an event failed. This is an internal error and should be reported to
customer support.
lcaErrNsDeferConfigUpdatesMgmntMode 31
The requested service cannot be provided in the current management mode. When you
encounter this error, set the system management mode to
lcaMgmtModePropagateConfigUpdates (0), and try the operation again. You can change
the system management mode by writing to the MgmtMode property of the System
object.
lcaErrNsSubscriptionDblimit 32
The NSS's event subscription table is full. This is an internal error, and should be
reported to customer support.
lcaErrNsSequence 33
A record from a binary external interface file or binary application image file was
received out of sequence. If you encounter the error, the XFB or APB file may be
corrupted.
lcaErrNsSegmentation 34
Segmentation is not supported, or there is a problem with segment order. This is an
internal error, and should be reported to customer support.
lcaErrNsChecksum 35
A checksum error occurred while transferring the binary external interface or binary
application image file to the NSS. If you encounter the error, the XFB or APB file may be
corrupted.
lcaErrNsSessionError 36
Invalid session handle or a session error. Make sure that sessions are begun and ended
in pairs, and are always part of an explicit transaction.
lcaErrNsNoNeuronId 37
An operation requiring a Neuron ID was attempted on a device with no Neuron ID. For
example, if you invoke the Wink method on a device whose Neuron ID has not been set
in the OpenLNS database, this exception will be thrown. In some other cases, this
exception may be thrown if a device’s Neuron ID has been set in the OpenLNS database,
but the device has not been commissioned. For example, if you read the
SelfDocumentation property of a device before that device has been commissioned, this
exception will be thrown, regardless of whether or not the device’s Neuron ID is set.
lcaErrNsProgramidMismatch 38
Program IDs do not match. This may occur if there is an incorrect or out-of-date program
version.