Manual

reinitialized. This reinitialization allows a network services tool to change
parameters, such as the number of priority slots, without the new valuesbeing
overwritten by the RTR-10 firmware.
Table 7. RTR-10 Router Transceiver IDs
ID Name Media
Bit Rate
(bps)
Input
Clock
01 (0x01) TP/XF-78 Transformer-isolated twisted pair 78k 10 MHz
03 (0x03) TP/XF-1250 Transformer-isolated twisted pair 1.25M 10 MHz
04 (0x04) TP/FT-10 Free Topology and Link Power 78k 10 MHz
05 (0x05) TP/RS485-39 EIA-485 twisted pair 39k 10 MHz
07 (0x07) RF-10 Radio Frequency (49 MHz) 4.9k 5 MHz
09 (0x09) PL-10 Power Line spread-spectrum 10k 10 MHz
10 (0x0A) TP/RS485-625 EIA-485 twisted pair 625k 10 MHz
11 (0x0B) TP/RS485-125 EIA-485 twisted pair 1.25M 10 MHz
12 (0x0C) TP/RS485-78 EIA-485 twisted pair 78k 10 MHz
16 (0x10) PL-20C Power Line C-Band 5.4k 10 MHz
17 (0x11) PL-20N Power Line C-Band 5.4k 10 MHz
18 (0x12) PL-30 Power Line A-Band 2.7k 10 MHz
24 (0x18) FO-10 Direct Connect 1.25M 10 MHz
27 (0x1B) DC-78 Direct Connect 78k 10 MHz
28 (0x1C) DC-625 Direct Connect 625k 10 MHz
29 (0x1D) DC-1250 Direct Connect 1.25M 10 MHz
30 (0x1E) Custom Custom Custom Custom
Notes:
Type 07 (0x07) can be used for Side B only.
PL-20C channels use the CENELEC protocol; PL-20N channels do not use the
CENELEC protocol.
Type 30 (0x1E) can be used for any transceiver type; the communications port is
initially defined as all inputs to prevent circuit conflicts. The side using type 30
(0x1E) must be reprogrammed through the other router side.