LonPoint Hardware Guide 9-5
Function Description
Processor/memory Neuron 3150 Chip, 10MHz, 56K flash memory
Service function Recessed service switch, service LED, power/wink LED. Dual tear-
off bar-code Neuron ID self-adhesive tag for application to red-line
drawings in the field
I/O 2 independent 12-bit resolution analog outputs
I/O type 0-10V into 1k•, minimum, or 0 to 20mA @ 0-12V
I/O resolution 0-10VDC: 2.5mV resolution
0-20mA: 5.0µA resolution
I/O isolation 100V, transformer isolation. Outputs are isolated from the input
power and the network but not from each other.
Transceiver type
FTT-10A with blocking capacitors for compatibility link power channel
Network connector Phone plug connector accessible from front panel
Input power 16-30VAC or VDC @ 4.2VA, internally isolated power supply
Mounting Type 1 or Type 1D Base Plate
Temperature -40 to +85°C, operating and non-operating
Humidity 10 to 95% RH @ 50°C
EMI FCC A, CE Mark
Safety agency UL 916
Function Blocks Node object (1), analog output open-loop actuator objects (2), digital
encoder controller objects (1), analog function block controller
objects (2), PID controller objects (2), type translators (3)
Software Configuration Wide variety of LONMARK Standard Configuration Parameter Types
supported by direct memory read/write function of LNS compatible
network management tools
AO-10 Module Software Settings
The software settings of the AO-10 module are described in the LonPoint
Application and Plug-In Guide.
Installing the AO-10 Module
Installation of the AO-10 module involves the following steps:
1. Ensure that the Base Plate has been wired and installed correctly, and is
securely fastened to the electrical enclosure.
2. Check for continuity on all network and power wiring. Ensure that the correct
actuators are connected to the correct Base Plate I/O terminals.
3. Make certain that all network channels are terminated with the correct number
and type of Terminator.
4. Insert the AO-10 module into the Base Plate by aligning the network access jack
on the AO-10 with the arrow head on the Base Plate (the arrow should point in
the direction of the jack), and then pressing firmly to ensure that the module is
properly seated in its mating Base Plate connector.