Owner's manual
3-12 Network Cabling and Connections
155 47.2 22 22 22 22 22 22 20 20 18 16 16 14
165 50.3 22 22 22 22 22 22 20 18 18 16 16 14
Table 3.4 Power Cabling Requirements in AWG (continued)
Load (VA)
Feet
Meters
10 15 20 25 30 40 55 75 100 130 180 200
185 56.4 22 22 22 22 22 22 20 18 18 16 14 14
215 65.5 22 22 22 22 22 20 20 18 16 16 14 14
230 70.1 22 22 22 22 22 20 18 18 16 16 14 14
235 71.6 22 22 22 22 22 20 18 18 16 14 14 14
250 76.2 22 22 22 22 22 20 18 18 16 14 14 12
265 80.8 22 22 22 22 20 20 18 16 16 14 14 12
295 89.9 22 22 22 22 20 20 18 16 16 14 12 12
300 91.4 22 22 22 22 20 18 18 16 16 14 12 12
340
103.6
22 22 22 20 20 18 18 16 14 14 12 12
365
111.3
22 22 22 20 20 18 16 16 14 14 12 12
375
114.3
22 22 22 20 20 18 16 16 14 12 12 12
395
120.4
22 22 20 20 20 18 16 16 14 12 12
400
121.9
22 22 20 20 18 18 16 16 14 12 12
420
128.0
22 22 20 20 18 18 16 14 14 12 12
470
143.3
22 22 20 20 18 18 16 14 14 12
475
144.8
22 22 20 20 18 16 16 14 14 12
500
152.4
22 22 20 18 18 16 16 14 12 12
545
166.1
22 20 20 18 18 16 16 14 12 12
580
176.8
22 20 20 18 18 16 14 14 12 12
595
181.4
22 20 20 18 18 16 14 14 12
630
192.0
22 20 18 18 18 16 14 14 12
635
193.5
22 20 18 18 16 16 14 14 12
750
228.6
22 20 18 18 16 16 14 12 12
755
230.1
20 20 18 18 16 14 14 12 12
AWG
795
242.3
20 20 18 16 16 14 14 12
865
263.7
20 18 18 16 16 14 14 12
945
288.0
20 18 18 16 16 14 12 12
1000
304.8
20 18 16 16 16 14 12 12
1010
307.8
20 18 16 16 14 14 12 12
1190
362.7
20 18 16 16 14 14 12
1200
365.8
18 18 16 16 14 12 12
1260
384.0
18 18 16 14 14 12 12
1375
419.1
18 16 16 14 14 12 12
1500
457.2
18 16 16 14 14 12
1590
484.6
18 16 14 14 14 12
1645
501.4
18 16 14 14 12 12